Pavel Hofman
2022-Sep-02 11:27 UTC
[Nut-upsuser] How to change shutdown notification threshold on Fortron UPS Champs (blazer_usb)?
Dne 29. 08. 22 v 12:53 Jim Klimov napsal(a):> The debug_min option is part of NUT 2.8.0, and your driver "screenshot" > was from 2.7.4. > > With older releases, you should manually ensure several `-D` options on > the driver command line to increase verbosity.Hi Jim, Thanks a lot. Is there any way to tell upsdrvctl to add the -D option when it starts the specific driver on that older version? I tried adding -D to upsdrvctl (in its systemd unit), to no avail. Thanks, Pavel.> > On Mon, Aug 29, 2022, 10:18 Pavel Hofman <pavel.hofman at ivitera.com > <mailto:pavel.hofman at ivitera.com>> wrote: > > > > Dne 19. 08. 22 v 12:49 Pavel Hofman napsal(a): > > Hi, > > > > I am trying to configure the shutdown threshold for Fortron UPS > Champs. > > > > upsc reports: > > > > Init SSL without certificate database > > battery.charge: 100 > > battery.voltage: 55.20 > > battery.voltage.high: 52.00 > > battery.voltage.low: 41.60 > > battery.voltage.nominal: 48.0 > > device.mfr: > > device.model: WPHVT2K0 > > device.type: ups > > driver.name <http://driver.name>: blazer_usb > > driver.parameter.pollinterval: 2 > > driver.parameter.port: /dev/hidraw2 > > driver.parameter.synchronous: no > > driver.version: 2.7.4 > > driver.version.internal: 0.12 > > input.current.nominal: 8.0 > > input.frequency: 50.0 > > input.frequency.nominal: 50 > > input.voltage: 234.5 > > input.voltage.fault: 234.5 > > input.voltage.nominal: 230 > > output.voltage: 229.7 > > ups.beeper.status: enabled > > ups.delay.shutdown: 30 > > ups.delay.start: 180 > > ups.firmware: 01060.07 > > ups.load: 46 > > ups.mfr: > > ups.model: WPHVT2K0 > > ups.productid: 5161 > > ups.status: OL > > ups.temperature: 26.3 > > ups.type: online > > ups.vendorid: 0665 > > > > > > Please note there is no battery.charge.low, the battery.charge is > > provided by the blazer_usb driver > > > https://networkupstools.org/docs/man/blazer_usb.html#_notes_for_the_previous_user_of_megatec_drivers > <https://networkupstools.org/docs/man/blazer_usb.html#_notes_for_the_previous_user_of_megatec_drivers> > > > > > > > I tried to configure override.battery.charge.low for the device in > > ups.conf (after ignorelb), nothing reported in upsc. > > > > I do not need any times, just being able to set? charge level or > voltage > > level at which NUTS will issue the shutdown command to my servers > > connected to the UPS a communicating with the nuts-server (their > > shutdown takes a while). I could not find any info how to do that > apart > > of > > > https://github.com/networkupstools/nut/issues/561#issuecomment-398791357 > <https://github.com/networkupstools/nut/issues/561#issuecomment-398791357> > > > which did not work for me (no battery.charge.low info appeared in > upcs > > after this setting and reloading all nuts-related daemons (server, > > client, monitor), nothing found in the logs. > > > > Thank you very much for any help or hints. > > > > I tried to increase debug_min = 10 in non-driver/global section of > ups.conf and no extra logs appeared in /var/log/syslog. Neither did > with > debug_min = 0 or 1, no effect. I do not know if the number should be > high or low, could not find it in any docs online. > > Thanks a lot, > > Pavel.