On 3/8/21 2:05 PM, Manuel Wolfshant wrote:> calibrating should not trigger nut
I agree, it shouldn't.
However, we did have NUT trigger a shutdown across everything and I'd
like to not have that happen again unless we're actually ONBATT + LOWBATT.
The only thing I can think of that may explain what happened was
UPS1 - ONBATT (calibrating)
UPS2 - ONLINE + LOWBATT (because of a bad battery)
UPS3 - ONLINE
it saw the ONBATT for 1 and the LOWBATT from 2 and triggered.
If that's the case, how do I prevent it from happening again?
nomad