On Dec 5, 2018, at 5:17 PM, Crispin Proctor <crispin.proctor at gmail.com>
wrote:>
> Hi folks,
>
>
> I have an APC Back-UPS XS 1400U which is reporting the wrong input and
output voltages.
> I am in the UK where our nominal voltage is 240 - not 110 :)
You're doing somewhat better than the XS 1200, and not quite as good as the
XS 1500. Since 1400 is between those two... :-)
http://new.networkupstools.org/ddl/APC/Back-UPS_XS_1200.html
http://new.networkupstools.org/ddl/APC/Back-UPS_XS_1500.html
>
> If I connect with parachute via USB it reports correctly.
>
> Is there a config I can update to tell it what it should be reporting? Some
wrong conversion?
>
I don't want to blame APC without doing due diligence, but a number of other
vendors seem to have errors in their HID report descriptors that produce similar
scaling problems. (It's the HID equivalent of not closing out a parenthesis
on a prior line.)
We do have a plan to add in HID descriptor patching:
https://github.com/networkupstools/nut/issues/169
To confirm if this is the same problem, can you kill usbhid-ups, then start it
back up with '-DDD'? (This is a little different than running the NUT
startup scripts, or upsdrvctl - just use 'ps auxww | grep [u]sbhid-ups'
to find the command line for the driver, then add in the debug flags. You can
grab both stdout and stderr, and send it to a log file. For Debian, it will
probably look something like this:
/lib/nut/usbhid-ups -a ups -DDD 2>&1 | tee
/tmp/APC_Back-UPS_XS_1400U.debug.log
It will run indefinitely, but we just need that first few pages before it goes
into the polling loop, so you can stop it with Ctrl-C.