Hello, Some more data about my experiences with riello_ups on iDialog 800 In orderr to avoid "stale data" problems, i tried to increase pollinterval in ups.conf: ==== ups.conf ====pollinterval = 4 maxretry = 3 [idg800] driver = riello_usb port = auto desc = "idg800" ================== It seems that pollinterval is ignored by the driver: # upsc idg800 | grep poll Init SSL without certificate database driver.parameter.pollinterval: 2 Moreover, i noted some message form the driver, when run in debug mode: 9.142152 read: FFFFFFF1 31 00 00 00 00 00 00 9.150151 read: FFFFFFF1 03 00 00 00 00 00 00 9.150168 in read: 48 9.150179 Get status Ok: read byte: 48 9.565285 send ok 9.566165 read: FFFFFFF0 00 00 00 00 00 00 00 9.574116 read: FFFFFFF7 02 22 20 15 32 30 30 9.582127 read: FFFFFFF5 30 30 3E 39 03 00 00 9.582153 in read: 12 9.582163 Get extended Ko: command not supported 10.490354 Communication with UPS is lost: status read failed! 10.901292 send ok 10.902128 read: FFFFFFF0 00 00 00 00 00 00 00 10.910099 read: FFFFFFF7 02 22 20 52 53 32 34 10.918083 read: FFFFFFF7 38 30 30 31 30 31 3F 10.926089 read: FFFFFFF7 35 30 3E 38 31 3F 35 Is "Communication with UPS is lost: status read failed!" something to be worried about? thanks, rob
On Feb 28, 2014, at 3:49 AM, Roberto Resoli wrote:> Hello, > Some more data about my experiences with riello_ups on iDialog 800 > > In orderr to avoid "stale data" problems, i tried to increase pollinterval in ups.conf: > > ==== ups.conf ====> pollinterval = 4 > maxretry = 3 > > [idg800] > driver = riello_usb > port = auto > desc = "idg800" > ==================> > It seems that pollinterval is ignored by the driver: > > # upsc idg800 | grep poll > Init SSL without certificate database > driver.parameter.pollinterval: 2It does seem to be hardcoded. I CC'd the author. Elio, do you know why this is set to 2 seconds?> Moreover, i noted some message form the driver, when run in debug mode: > > 9.142152 read: FFFFFFF1 31 00 00 00 00 00 00 > 9.150151 read: FFFFFFF1 03 00 00 00 00 00 00 > 9.150168 in read: 48 > 9.150179 Get status Ok: read byte: 48 > 9.565285 send ok > 9.566165 read: FFFFFFF0 00 00 00 00 00 00 00 > 9.574116 read: FFFFFFF7 02 22 20 15 32 30 30 > 9.582127 read: FFFFFFF5 30 30 3E 39 03 00 00 > 9.582153 in read: 12 > 9.582163 Get extended Ko: command not supported > 10.490354 Communication with UPS is lost: status read failed! > 10.901292 send ok > 10.902128 read: FFFFFFF0 00 00 00 00 00 00 00 > 10.910099 read: FFFFFFF7 02 22 20 52 53 32 34 > 10.918083 read: FFFFFFF7 38 30 30 31 30 31 3F > 10.926089 read: FFFFFFF7 35 30 3E 38 31 3F 35 > > Is "Communication with UPS is lost: status read failed!" something to be worried about?Ideally the UPS wouldn't do that, but if it reconnects... -- Charles Lepple clepple at gmail
Reasonably Related Threads
- riello_usb driver: randomly not working and usbfs flooding syslog
- riello_usb driver: randomly not working and usbfs flooding syslog
- riello_usb driver: randomly not working and usbfs flooding syslog
- riello_usb, idg 800 and ups shutdown
- Je ne parviens pas à faire communiquer mon UPS avec HomeAssistant