2016-Dec-07 18:35 UTC
[Nut-upsdev] nut-git reporting 24 Volts with CP1350PFCLCD -- is that correct?
Arjen, all, I just built and installed network-ups-tools-git-v2.7.4.r161.g7bf209a on Archlinux for a CyberPower CP1350PFCLCD ups. After hitting the FAQ 29. "My USB UPS is supported but doesn?t work!" udev issue because the UPS was plugged in when nut was installed bug, running upsc I get: battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 20 battery.mfr.date: CPS battery.runtime: 3450 battery.runtime.low: 300 battery.type: PbAcid battery.voltage: 24.0 battery.voltage.nominal: 24 device.mfr: CPS device.model: CP1350PFCLCD device.serial: 000000000000 device.type: ups driver.name: usbhid-ups driver.parameter.pollfreq: 30 driver.parameter.pollinterval: 2 driver.parameter.port: /dev/hiddev0 driver.parameter.synchronous: no driver.version: 2.7.4-161-g7bf209a driver.version.data: CyberPower HID 0.4 driver.version.internal: 0.42 input.transfer.high: 139 input.transfer.low: 88 input.voltage: 121.0 input.voltage.nominal: 120 output.voltage: 137.0 ups.beeper.status: enabled ups.delay.shutdown: 20 ups.delay.start: 30 ups.load: 11 ups.mfr: CPS ups.model: CP1350PFCLCD ups.productid: 0501 ups.realpower.nominal: 810 ups.serial: 000000000000 ups.status: OL ups.test.result: No test initiated ups.timer.shutdown: -60 ups.timer.start: -60 ups.vendorid: 0764 Really?? battery.voltage: 24.0 battery.voltage.nominal: 24 That looks suspicious like there is a scaling issue (unless there are two batteries in series in this thing). Also I woulds suspect 'battery.voltage' to be 26.x if that was the case with new batteries. What say the nut experts? Is this right? If not, what can I send you to help with the scaling? I recall running tests and capturing data for Arjen 8-9 years ago with another CyberPower CP1000AVRLCD that allowed the voltage to be set correctly. I don't know if that is needed with this model as well. If so, let me know (and remind me what you need -- it's been a while), and I'm happy to send it. Note: https://github.com/networkupstools/nut/issues/140 referenced in FAQ 29 is NOT fixed. I just did a fresh pull and build from today's git source, and I was still bitten by this bug (unplugged and replugged the usb cable and all was well) -- David C. Rankin, J.D.,P.E.
Charles Lepple
2016-Dec-08 00:23 UTC
[Nut-upsdev] nut-git reporting 24 Volts with CP1350PFCLCD -- is that correct?
On Dec 7, 2016, at 1:35 PM, David C. Rankin <drankinatty at suddenlinkmail.com> wrote:> I just built and installed network-ups-tools-git-v2.7.4.r161.g7bf209a on > Archlinux for a CyberPower CP1350PFCLCD ups. After hitting the FAQ 29. "My USB > UPS is supported but doesn?t work!" udev issue because the UPS was plugged in > when nut was installed bug, running upsc I get:...> Really?? > > battery.voltage: 24.0 > battery.voltage.nominal: 24 >For a CP1500PFLCD: http://lists.alioth.debian.org/pipermail/nut-upsuser/2014-March/008948.html and http://lists.alioth.debian.org/pipermail/nut-upsuser/2014-April/008969.html Based on the latter message, I don't think we can fix that. (I still haven't gotten around to writing a HID descriptor patcher, which might help with some of the other voltages.) See also http://networkupstools.org/ddl/Cyber_Power_Systems/CP1500PFCLCD.html (and the other entries one level up).> Note: https://github.com/networkupstools/nut/issues/140 referenced in FAQ 29 > is NOT fixed. I just did a fresh pull and build from today's git source, and I > was still bitten by this bug (unplugged and replugged the usb cable and all > was well)Is it some variant of this issue? The Arch install scripts should tell udevd to reload somehow. https://bugs.launchpad.net/ubuntu/+source/nut/+bug/1540008 Since the NUT project doesn't really control the distro-specific scripts, we closed the issue based on the distro-specific bugs that we knew about at the time. If there is one filed against Arch, we can add that to the list.