2006-Feb-06 02:00 UTC
[Nut-upsdev] 2.0.3-pre2: Spurious UPS UPS@localhost battery is low ?
Hi there, [ http://www.contribs.org/bugzilla/show_bug.cgi?id=654 ] I just received this: Broadcast message from nut (Sat Feb 4 04:02:45 2006): UPS UPS@localhost battery is low and Feb 4 04:02:45 bigted upsmon[11532]: UPS UPS@localhost battery is low Feb 4 04:02:45 bigted wall[4032]: wall: user nut broadcasted 1 lines (34 chars) but I believe this looks o.k., except for the input voltage value. Is it meant to be a largish negative number (checked again and got -6301.0). The system has been running on stable (well, o.k. domestic) line power. [gordonr@bigted]$ upsc UPS@localhost battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 50 battery.date: 3150/08/01 battery.mfr.date: 2005/01/20 battery.runtime: 322 battery.runtime.low: 120 battery.temperature: 302.0 battery.voltage: 13.0 battery.voltage.nominal: 12.0 driver.name: newhidups driver.version: 2.0.3-pre2 driver.version.data: APC HID 0.8 driver.version.internal: 0.28 input.voltage: -6301.0 input.voltage.nominal: 230 output.voltage: 230.0 output.voltage.target.line: 230.0 ups.beeper.status: enabled ups.delay.shutdown: -1 ups.firmware: 814.s3.I ups.firmware.aux: s3 ups.load: 73.0 ups.mfr: American Power Conversion ups.mfr.date: 2005/01/20 ups.model: Back-UPS BF500 ups.serial: AB0504244053 ups.status: OL ups.temperature: 302.0 ups.test.result: No test initiated If you would like this in the bug tracker instead, please let me know. It's certainly not easy to find from http://www.networkupstools.org/ :-) Gordon
Peter Selinger
2006-Feb-06 08:37 UTC
[Nut-upsdev] 2.0.3-pre2: Spurious UPS UPS@localhost battery is low ?
Hi Gordon, Just looking at the numbers, it looks like you might have found a bug in the voltage conversion function that might be related to the signedness/unsignedness of numbers; note that -6301.0 + 65536/10 252.6. The latter could be a legitimate voltage, but seems unusually high for any country (your "nominal" voltage is 230). I am also worried about your battery.temperature, ups.temperature, and battery.date. It looks like we might need to tweak the driver a bit for your unit. (This seems to be a different UPS than the one you wrote about last week?) Could you again run "./drivers/newhidups -u root -DD -a UPS auto" and post the "Path" lines, so that I can see the raw, unconverted values of these variables? Thanks, -- Peter Gordon Rowell wrote:> > Hi there, > > [ http://www.contribs.org/bugzilla/show_bug.cgi?id=654 ] > > I just received this: > > Broadcast message from nut (Sat Feb 4 04:02:45 2006): > > UPS UPS@localhost battery is low > > and > > Feb 4 04:02:45 bigted upsmon[11532]: UPS UPS@localhost battery is low > Feb 4 04:02:45 bigted wall[4032]: wall: user nut broadcasted 1 lines (34 > chars) > > but I believe this looks o.k., except for the input voltage value. Is it > meant to be a largish negative number (checked again and got -6301.0). > > The system has been running on stable (well, o.k. domestic) line power. > > [gordonr@bigted]$ upsc UPS@localhost > battery.charge: 100 > battery.charge.low: 10 > battery.charge.warning: 50 > battery.date: 3150/08/01 > battery.mfr.date: 2005/01/20 > battery.runtime: 322 > battery.runtime.low: 120 > battery.temperature: 302.0 > battery.voltage: 13.0 > battery.voltage.nominal: 12.0 > driver.name: newhidups > driver.version: 2.0.3-pre2 > driver.version.data: APC HID 0.8 > driver.version.internal: 0.28 > input.voltage: -6301.0 > input.voltage.nominal: 230 > output.voltage: 230.0 > output.voltage.target.line: 230.0 > ups.beeper.status: enabled > ups.delay.shutdown: -1 > ups.firmware: 814.s3.I > ups.firmware.aux: s3 > ups.load: 73.0 > ups.mfr: American Power Conversion > ups.mfr.date: 2005/01/20 > ups.model: Back-UPS BF500 > ups.serial: AB0504244053 > ups.status: OL > ups.temperature: 302.0 > ups.test.result: No test initiated > > If you would like this in the bug tracker instead, please let me know. > > It's certainly not easy to find from http://www.networkupstools.org/ :-) > > Gordon > > _______________________________________________ > Nut-upsdev mailing list > Nut-upsdev@lists.alioth.debian.org > http://lists.alioth.debian.org/mailman/listinfo/nut-upsdev >
Charlie Brady
2006-Feb-06 16:29 UTC
[Nut-upsdev] 2.0.3-pre2: Spurious UPS UPS@localhost battery is low ?
On Mon, 6 Feb 2006, Peter Selinger wrote:> Just looking at the numbers, it looks like you might have found a bug > in the voltage conversion function that might be related to the > signedness/unsignedness of numbers; note that -6301.0 + 65536/10 > 252.6. The latter could be a legitimate voltage, but seems unusually > high for any country (your "nominal" voltage is 230).But used to be, quite recently, 240V. 252.6V is within standard tolerance - just. -- Charlie
Maybe Matching Threads
- 2.0.3-pre2: Spurious UPS UPS@localhost battery is
- [LLVMdev] attaching metadata to llvm::Argument
- [LLVMdev] attaching metadata to llvm::Argument
- [LLVMdev] Why BinaryOperator::Create requires same argument types for shifts?
- [LLVMdev] Why BinaryOperator::Create requires same argument types for shifts?