Hi,
2005/12/27, Miguel P.C. <mpcolino@pop.isdefe.es>:>
> Hello.
>
> I've just reinstalled a server that was with RH9 and now it is with
> Fedora Core 4.
> I'm using the nut package that comes with the distro, version 2.0.2 to
> check through serial port a MGE Galaxy PW (comm card 66060).
>
> Everything goes fine except for a little thing, when checking the UPS
> with '#upsc ups@localhost' I receive a line like this:
> 'ups.status: OL OFF'
> It used to be:
> 'ups.status: OL'
>
> This makes nagios complain giving an error in which says:
> 'UPS CRITICAL - Status=Off Utility=386,0V Batt=100,0% Load=40,0%'
> (Also with the latest version of
>
> My questions are:
> Has this changed in upsd?, perhaps in mge driver?
> Should I change my configuration in any way to readapt it to the new
> version?
> Is this a normal behaviour?
this is part of the regression set in mge-utalk.
As I've stated in my christmas mail [1], this (mge-utalk correction) is part
of the last remaining points for 2.0.3.
Sorry for the inconvenience.
Arnaud Quette
--
[1]
http://lists.alioth.debian.org/pipermail/nut-upsuser/2005-December/000566.html
--
Linux / Unix Expert - MGE UPS SYSTEMS - R&D Dpt
Network UPS Tools (NUT) Project Leader - http://www.networkupstools.org/
Debian Developer - http://people.debian.org/~aquette/
OpenSource Developer - http://arnaud.quette.free.fr/