Displaying 20 results from an estimated 142 matches for "finaldelay".
2023 Oct 27
2
FSD sequence: Waiting for bigger and slower clients before cutting power
...cs/user-manual.chunked/
Configuration_notes.html#UPS_shutdown, and also reading upsmon.c, when a UPS
goes OB LB (assuming we have a single UPS connected to a primary and supplying
power to the primary and some number of secondaries), the primary notifies the
secondaries, the secondaries wait for FINALDELAY and then execute SHUTDOWNCMD
immediately followed by exiting, thereby disconnecting from the primary, and
the primary, after seeing all secondaries disconnect, proceed with its
shutdown (only waiting for FINALDELAY), which ends with telling the UPS to cut
the power (without delay too, right?)....
2023 Oct 27
2
FSD sequence: Waiting for bigger and slower clients before cutting power
...figuration_notes.html#UPS_shutdown, and also reading upsmon.c, when a
> UPS
> goes OB LB (assuming we have a single UPS connected to a primary and
> supplying
> power to the primary and some number of secondaries), the primary notifies
> the
> secondaries, the secondaries wait for FINALDELAY and then execute
> SHUTDOWNCMD
> immediately followed by exiting, thereby disconnecting from the primary,
> and
> the primary, after seeing all secondaries disconnect, proceed with its
> shutdown (only waiting for FINALDELAY), which ends with telling the UPS to
> cut
> the powe...
2008 Feb 07
1
power off before shutdown complete
Hi,
I have simple configuration: one master with one UPS connected
via serial port, and five slaves. When battery is low and master
set FSD on UPS, then after few seconds it get from all slaves:
"disconnected (read failure)" and start shutdown and power off
before slave shutdown complete, that need about 90 seconds. I
don't understand, why slaves disconnected before shutdown go
near
2009 Aug 26
2
Linux and the APC Back-UPS ES
...bug : my ups run out of battery before the end of
> the shutdown process (a full shutdown take less than 2 minutes).
>
> Is there a way to "start the shutdown process earlier", or to change the
> battery.charge.low or battery.runtime.low variables?
>
> I try to set a FinalDelay to 0, but it doesn't help.
>
> Do you have any idea to help me?
>
> Thank you.
2023 Oct 31
1
FSD sequence: Waiting for bigger and slower clients before cutting power
...down, and also reading upsmon.c, when a
> > UPS
> > goes OB LB (assuming we have a single UPS connected to a primary and
> > supplying
> > power to the primary and some number of secondaries), the primary notifies
> > the
> > secondaries, the secondaries wait for FINALDELAY and then execute
> > SHUTDOWNCMD
> > immediately followed by exiting, thereby disconnecting from the primary,
> > and
> > the primary, after seeing all secondaries disconnect, proceed with its
> > shutdown (only waiting for FINALDELAY), which ends with telling the UPS...
2020 Jul 22
1
AVRX750/500 issues
...Connection to pi closed.
################
I ran this command under two sets of conditions:
- UPS plugged in to the mains
- UPS unplugged from the mains, then plugging it back in approximately
60 seconds after it turned off
In both cases, the Pi shut down cleanly after approximately 5 seconds (FINALDELAY?), and the UPS turned off after approximately 25 seconds (FINALDELAY + the default offdelay?) However, the UPS never came back up.
Second Experiment
#################
$ sudo upsdrvctl shutdown
Network UPS Tools - UPS driver controller 2.7.4 Network UPS Tools - Generic HID driver 0.41 (2.7.4) USB c...
2011 Jul 21
1
Unexpected shutdown begins for WOW-500U
...rom source on Xenserver 5.6 SP2
(Linux xen-home 2.6.32.12-0.7.1.xs5.6.100.323.170596xen #1 SMP Fri Apr 8
07:25:07 EDT 2011 i686 athlon i386 GNU/Linux), my UPS is Powercom WOW--500U
FW3.A4. All works almost fine but here are some troubles: when I pull the
plug then upsd immediately starts (after FINALDELAY delaying) the procedure
of shutdown as if UPS have low battery. What I see after pulling the plug:
./upsc xen-home battery.charge
72
./upsc xen-home ups.status
OB DISCHRG
OB status is correct but why is there DISCHRG status?! This flag, as I
think, cause immediately begin of shutdown although...
2011 Jul 19
2
KIN-1500AP RM + Windows 2008 64-bit Standard R2 SP1 (nut 2.6.1)
...OWS\\system32\\shutdown.exe -s -t 0"
NOTIFYCMD /sbin/upssched
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG "C:\\killpower"
NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
upssched.conf:
*
*
CMDSCRIPT /bin/upssched-cmd
AT ONBATT * START-TIMER onbattwarn 10
AT ONLINE * CANCEL-TIMER onbattwarn
AT LOWBATT * EXECUTE lowbattwarn
AT ONBATT * START-TIMER timeshutdown 100
AT ONLINE * CANCEL-TIMER timeshutdown
After start I can see couple neutral events:
ups...
2010 Sep 14
2
using NUT on centos 5
Hi!
Trying to set up NUT on Centos 5 to monitor a CyberPower 1500AVR UPS.
There seem to be many documents, all of which seem to be not fully consistent
with each other, and most of them aren't up to date.
I'm guessing I should be using udev rather than hal, but I'm somewhat
stumped on how to figure out what device it should be monitoring. there
are a bunch of udev rules installed
2016 Oct 26
2
setting up CYBERPOWER CP1500PFCLCD
...SYNC set to 15
Level INFO 10/26/2016 10:46:17 Config Load: DEADTIME set to 15
Level INFO 10/26/2016 10:46:17 Config Load: RBWARNTIME set to
43200
Level INFO 10/26/2016 10:46:17 Config Load: NOCOMMWARNTIME set to
300
Level INFO 10/26/2016 10:46:17 Config Load: FINALDELAY set to 5
Level CRITICAL 10/26/2016 10:46:17 Fatal error: insufficient power
configured!
Level CRITICAL 10/26/2016 10:46:17 Sum of power values........: 0
Level CRITICAL 10/26/2016 10:46:17 Minimum value (MINSUPPLIES): 1
Level CRITICAL 10/26/2016 10:46:17
Edit your upsmon.conf a...
2018 May 09
1
how to use multiple UPS with timers
Yes both UPS units are on different power supplies. MINSUPPLIES is set to 1.
Afaik NUT waits for OB and LB before shutting down the system. Is there a way to change this behavior to only wait for OB?
Then I would use FINALDELAY in case the power outage doesn't last long.
I already tried to change the battery.runtime.low setting over the webinterface of the CS121 (snmp is readonly) but with our AEG UPS, this didn't work as expected(seems like a firmware bug) and I need to work around this problem.
I'm already...
2006 Sep 13
2
POWERDOWNFLAG (/etc/killpower) does not contain the upsmon magic string!!!
...fectly but when i start upsmon i recive the message:
POWERDOWNFLAG (/etc/killpower) does not contain the upsmon magic string
My upmon.conf contain:
MONITOR myups@theseo 1 orion91 carlos81 master
SHUTDOWNCMD "/sbin/shutdown -h +0"
HOSTSYNC 15
POWERDOWNFLAG /etc/killpower
FINALDELAY 5
My killpower scrit in /etc/killpower contain:
#!/bin/bash
if (test -f /etc/killpower)
then
echo "Killing the power, bye!"
/sbin/upsdrvctl shutdown
sleep 120
# uh oh... the UPS poweroff failed!
# you probably should reboot h...
2010 Nov 16
2
Shutdown script does not trigger
...ssword = ****
actions = SET
instcmds = ALL
[upsmon]
password = ****
upsmon master
/etc/nut/upsmon.conf :
RUN_AS_USER nut
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
RBWARNTIME 43200
FINALDELAY 5
MONITOR dell at localhost 1 upsmon **** master
/etc/nut/upssched.conf :
CMDSCRIPT /etc/nut/sched/upssched.sh (this script exists but seems never
to be executed...)
PIPEFN /etc/nut/sched/upssched.pipe
LOCKFN /etc/nut/sched/upssched.lock
# the timers, here 30 sec after the ONBATT (ups on battery...
2018 Feb 26
2
[networkupstools/nut] Riello IDG400 wrong values & not powering off (#530)
...here other variables that are affected?
(I don't think the IDG400 is covered in the protocol documentation that the NUT project received a while back.)
>
> For the point number 2, as we know NUT perfomrs the shutdown after battery low signal with a delay of 5 seconds as specified in the FINALDELAY.
> Is this correct?
Right, NUT tells the computer to shut down, but it also typically sends a shutdown signal to the UPS. Does the IDG400 also respond to the same shutdown command as others?
2012 Apr 11
1
NOTIFYCMD doesn't work from Windows service
...ONLINE
NOTIFYMSG ONBATT ONBATT
NOTIFYMSG LOWBATT LOWBATT
NOTIFYMSG FSD FSD
NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
NOTIFYFLAG FSD SYSLOG+WALL+EXEC
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
I also tried
NOTIFYCMD C:\\NUT\\shutdown.bat
NOTIFYCMD "\"C:\\NUT\\shutdown.bat""
with no success.
NUT 2.6.1-1 with replaced upsmon.exe from here: http://fbohe.free.fr/upsmon.exe.
Windows 2003 R2 x64 Rusian.
Master server is Debian Squeeze.
Regards,
Dmitry
2011 Jun 08
2
Misconfiguration of Windows MSI installer 2.6.0-1 with my Powerware 5115 connected via USB port
...PLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /sbin/upssched
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
*upssched.conf:*
CMDSCRIPT /bin/upssched-cmd
AT ONBATT * START-TIMER onbattwarn 10
AT ONLINE * CANCEL-TIMER onbattwarn
AT LOWBATT * EXECUTE lowbattwarn
AT ONBATT * START-TIMER timeshutdown 100
AT ONLINE * CANCEL-TIMER timeshutdown
There are huge count of windows events such as &quo...
2020 Jan 01
2
Belkin USB UPS Not Turning Off
...*** master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /home/android/nutShutdown.sh
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYFLAG ONBATT WALL+EXEC
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
########### /etc/nut/upssched.conf ###########
CMDSCRIPT /bin/upssched-cmd
########### <scriptname> ###########
Cannot access <scriptname>
########### /etc/hosts.allow ###########
########### ps aux ###########
nut 2333 0.0 0.0 3336 696...
2006 Feb 14
3
Master privileges unavailable on UPS
...YSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
NOTIFYFLAG FSD SYSLOG+WALL+EXEC
NOTIFYFLAG COMMOK SYSLOG+WALL+EXEC
NOTIFYFLAG COMMBAD SYSLOG+WALL+EXEC
NOTIFYFLAG SHUTDOWN SYSLOG+WALL+EXEC
NOTIFYFLAG REPLBATT SYSLOG+WALL+EXEC
NOTIFYFLAG NOCOMM SYSLOG+WALL+EXEC
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
What am I missing?
Thanks!
--
David Benfell, LCP
benfell@parts-unknown.org
---
Resume available at http://www.parts-unknown.org/
2009 Nov 15
3
two MGE Ellipse 1500 ups via usb
Hi,
I've got two MGE Ellipse 1500 UPS connected via usb to an ubuntu
jaunty system with nut and libupsclient1 2.4.1-2ubuntu4.
As soon as I start the driver for the second one, they start fighting
each other and I get no data. I found an older post to this list that
said: If you want to monitor multiple UPSes through usbhid-ups, you
*must* make sure that each one can be uniquely identified
2017 Oct 18
2
debian 8 "jessie" nut 2.7.2 slaves not shutting down
OS name and version,
MASTER SYSTEM has three APC smart UPS 3000 UPS connected via USB
debian 8 "jessie" Linux pdxvhtst01 3.16.0-4-amd64 #1 SMP Debian 3.16.43-2+deb8u5 (2017-09-19) x86_64 GNU/Linux
SLAVE SYSTEMS monitoring MASTER via IP
debian 8 "jessie" Linux geaaetst01