Displaying 20 results from an estimated 59 matches for "configapparentpower".
2007 Aug 11
1
apc-hid.c: watts_to_av_conversion
...t;,
HU_FLAG_OK, watts_to_av_conversion }, /* CyberPower */
to
{ "ups.realpower.nominal", 0, 0, "UPS.Output.ConfigActivePower", NULL,
"%.0f", HU_FLAG_OK, NULL }, /* CyberPower */
Chances are, it also supports
{ "ups.power.nominal", 0, 0, "UPS.Output.ConfigApparentPower", NULL,
"%.0f", HU_FLAG_OK, NULL }, /* CyberPower */
so that may be worthwhile adding too.
Best regards, Arjen
--
Eindhoven - The Netherlands
Key fingerprint - 66 4E 03 2C 9D B5 CB 9B 7A FE 7E C1 EE 88 BC 57
2012 Jul 18
1
Problem connecting to eaton ups. No matching HID UPS found. Driver failed to start(exit status=1)
...e: 0
3.952939 Path: UPS.BatterySystem.Charger.PresentStatus.VoltageTooLow, Type: Feature, ReportID: 0x03, Offset: 8, Size: 8, Value: 0
3.953381 Path: UPS.BatterySystem.Charger.PresentStatus.VoltageTooLow, Type: Input, ReportID: 0x03, Offset: 8, Size: 8, Value: 0
4.002973 Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature, ReportID: 0x0d, Offset: 0, Size: 16, Value: 1600
4.003390 Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID: 0x0d, Offset: 16, Size: 8, Value: 50
4.048948 Path: UPS.Flow.[4].ConfigVoltage, Type: Feature, ReportID: 0x12, Offset: 0, Size: 8, Value: 230
4.128988 Path...
2006 Sep 22
1
Ablerex 625L USB version
...ure, Value: 0.000000
Path: 00860004.Flow.iSerialNumber, Type: Feature, Value: 0.000000
Path: 00860004.Flow.FlowID, Type: Feature, Value: 0.000000
Path: 00860004.Flow.ConfigVoltage, Type: Feature, Value: 0.000000
Path: 00860004.Flow.ConfigFrequency, Type: Feature, Value: 0.000000
Path: 00860004.Flow.ConfigApparentPower, Type: Feature, Value: 0.000000
Path: 00860004.Flow.ConfigActivePower, Type: Feature, Value: 0.000000
Path: 00860004.Flow.DelayBeforeStartup, Type: Feature, Value: 0.000000
Path: 00860004.Flow.DelayBeforeShutdown, Type: Feature, Value: 0.000000
Path: 00860004.BatterySystem.BatterySystemID, Type: Fe...
2008 Apr 01
1
Incorrect battery status on MGE Pulsar M 3000
...tage, Type: Feature, ReportID: 0x15, Offset: 0,
Size: 8, Value: 230.000000
Path: UPS.Flow.[1].FlowID, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 8,
Value: 1.000000
Path: UPS.Flow.[4].ConfigActivePower, Type: Feature, ReportID: 0x74, Offset:
0, Size: 16, Value: 2700.000000
Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature, ReportID: 0x75, Offset:
0, Size: 16, Value: 3000.000000
Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID: 0x36, Offset: 0,
Size: 8, Value: 50.000000
Path: UPS.Flow.[4].ConfigPercentLoad, Type: Feature, ReportID: 0x16, Offset:
0, Size: 8, Value: 100.000000
Path: UPS.Flo...
2018 Sep 01
0
Adding drivers to NUT?
...Summary.WarningCapacityLimit
- battery.charge.low / UPS.PowerSummary.RemainingCapacityLimit
2. Do the following ones return punctual data, or only the nominal
value? If the latter, do they change, or they are static?
- ups.realpower / UPS.Output.ConfigActivePower
- ups.realpower / UPS.Flow.ConfigApparentPower
3. Are the following ones static?
- input.voltage.nominal / UPS.Input.ConfigVoltage
- input.voltage.nominal / UPS.Flow.ConfigVoltage
- battery.voltage.nominal / UPS.PowerSummary.ConfigVoltage
- battery.voltage.nominal / UPS.BatterySystem.Battery.ConfigVoltage
4. What's the reason fo...
2016 May 03
2
New UPS Support: Eaton 5S 1000
Oops... changing that to --with-user=nut solved one problem. I have the
driver, upsd and upsmon running now. Thank you!
Now I'm back to another issue, every 2 seconds I get in the logs:
May 3 13:45:23 myhost upsd[2587]: Connected to UPS [eaton]:
usbhid-ups-eaton
It seems happy to do this forever.
On Tue, May 3, 2016 at 8:17 AM, Charles Lepple <clepple at gmail.com> wrote:
> On
2015 Jun 07
2
libusb_get_string: invalid argument
...ature, ReportID:
0x10, Offset: 0, Size: 8, Value: 0
0.946206 Path: UPS.Flow.ConfigVoltage, Type: Feature, ReportID:
0x01, Offset: 0, Size: 8, Value: 120
0.962957 Path: UPS.Flow.ConfigFrequency, Type: Feature,
ReportID: 0x02, Offset: 0, Size: 8, Value: 60
0.979721 Path: UPS.Flow.ConfigApparentPower, Type: Feature,
ReportID: 0x03, Offset: 0, Size: 16, Value: 900
0.996456 Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown,
Type: Feature, ReportID: 0x15, Offset: 0, Size: 16, Value: 65535
1.013330 Path: UPS.OutletSystem.Outlet.ffff0091, Type: Feature,
ReportID: 0x51, Offset: 0, Size:...
2016 May 04
2
New UPS Support: Eaton 5S 1000
...e: 0
4.602005 Path: UPS.BatterySystem.Charger.PresentStatus.VoltageTooLow,
Type: Feature, ReportID: 0x03, Offset: 8, Size: 8, Value: 0
4.602014 Path: UPS.BatterySystem.Charger.PresentStatus.VoltageTooLow,
Type: Input, ReportID: 0x03, Offset: 8, Size: 8, Value: 0
4.649995 Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature,
ReportID: 0x0d, Offset: 0, Size: 16, Value: 1000
4.650013 Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID:
0x0d, Offset: 16, Size: 8, Value: 60
4.693980 Path: UPS.Flow.[4].ConfigVoltage, Type: Feature, ReportID:
0x12, Offset: 0, Size: 8, Value: 115
4.773997 Path...
2017 Dec 18
2
Tripp-Lite BCPERS450 shutdown/restart problems
...st, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 0
0.069120 Path: UPS.Flow.ConfigVoltage, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 120
0.069695 Path: UPS.Flow.ConfigFrequency, Type: Feature, ReportID: 0x02, Offset: 0, Size: 8, Value: 60
0.070252 Path: UPS.Flow.ConfigApparentPower, Type: Feature, ReportID: 0x03, Offset: 0, Size: 16, Value: 450
0.070916 Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown, Type: Feature, ReportID: 0x15, Offset: 0, Size: 16, Value: 65535
0.071567 Path: UPS.OutletSystem.Outlet.ffff00bc, Type: Feature, ReportID: 0xe0, Offset: 0, Size: 16, Val...
2015 Jun 09
0
libusb_get_string: invalid argument
...ature, ReportID:
0x10, Offset: 0, Size: 8, Value: 0
1.003749 Path: UPS.Flow.ConfigVoltage, Type: Feature, ReportID:
0x01, Offset: 0, Size: 8, Value: 120
1.020490 Path: UPS.Flow.ConfigFrequency, Type: Feature,
ReportID: 0x02, Offset: 0, Size: 8, Value: 60
1.037271 Path: UPS.Flow.ConfigApparentPower, Type: Feature,
ReportID: 0x03, Offset: 0, Size: 16, Value: 900
1.054007 Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown,
Type: Feature, ReportID: 0x15, Offset: 0, Size: 16, Value: 65535
1.070622 Path: UPS.OutletSystem.Outlet.ffff0091, Type: Feature,
ReportID: 0x51, Offset: 0, Size:...
2006 Feb 10
1
newhidups capture - Atlantis-Land HID UPS
Hello Charles!
As promised, I just checked out the CVS and recompiled everything. In
the attached .txt is what is coming out from my UPS. I am wondering
about all those zeroes.
Also, this morning I plan to connect the UPS to a Win box running the
monitoring program supplied with the UPS (UPSilon2000) and a USB sniffer
program. If you have any suggestions on what to look for in the data,
2006 Jun 14
3
Trouble Configuring NUT with Gamatronic USB
Hi
I am running FC5 with nut coming from the fc5 extras repositories. I
am trying to configure a Gamatronic D-Compact ups. The cable that came
with the ups has a serial connector on one end and a usb on the other.
cat /proc/bus/usb/devices produces
T: Bus=01 Lev=01 Prnt=01 Port=01 Cnt=01 Dev#= 4 Spd=1.5 MxCh= 0
D: Ver= 1.10 Cls=00(>ifc ) Sub=00 Prot=00 MxPS= 8 #Cfgs= 1
P:
2016 Dec 07
1
Incorrect scale on values for TRIPPLITE UPS
...eportID: 0x31, Offset: 0, Size: 16, Value: 0.001214
0.856189 Path: UPS.Flow.ConfigVoltage, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 120
0.869186 Path: UPS.Flow.ConfigFrequency, Type: Feature, ReportID: 0x02, Offset: 0, Size: 8, Value: 60
0.878190 Path: UPS.Flow.ConfigApparentPower, Type: Feature, ReportID: 0x03, Offset: 0, Size: 16, Value: 1300
0.882185 Path: UPS.PowerConverter.Input.Voltage, Type: Feature, ReportID: 0x18, Offset: 0, Size: 16, Value: 0.001214
0.886188 Path: UPS.PowerConverter.Input.Frequency, Type: Feature, ReportID: 0x19, Offset: 0, Size: 16,...
2008 Feb 24
2
usbhid-ups using wrong value for battery voltage for Pulsar Evolution 500?
...ffset:
16, Size: 16, Value: 119.000000
And some flow information:
Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID: 0x14,
Offset: 8, Size: 8, Value: 60.000000
Path: UPS.Flow.[4].ConfigActivePower, Type: Feature, ReportID: 0x14,
Offset: 16, Size: 16, Value: 350.000000
Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature, ReportID: 0x14,
Offset: 32, Size: 16, Value: 500.000000
Path: UPS.Flow.[4].ConfigCurrent, Type: Feature, ReportID: 0x14,
Offset: 48, Size: 16, Value: 4.160000
Path: UPS.Flow.[4].ConfigVoltage, Type: Feature, ReportID: 0x15,
Offset: 0, Size: 16, Value: 120.000000
Path: UPS.PowerConve...
2018 Sep 03
0
Adding drivers to NUT?
...y.charge.low / UPS.PowerSummary.RemainingCapacityLimit
> > 2. Do the following ones return punctual data, or only the nominal
> > value? If the latter, do they change, or they are static?
> > - ups.realpower / UPS.Output.ConfigActivePower
> > - ups.realpower / UPS.Flow.ConfigApparentPower
> > 3. Are the following ones static?
> > - input.voltage.nominal / UPS.Input.ConfigVoltage
> > - input.voltage.nominal / UPS.Flow.ConfigVoltage
> > - battery.voltage.nominal / UPS.PowerSummary.ConfigVoltage
> > - battery.voltage.nominal / UPS.BatterySystem...
2015 Jun 09
2
libusb_get_string: invalid argument
On Jun 8, 2015, at 8:23 PM, Greg Hersch <hersch.greg at gmail.com> wrote:
> Hi Charles. I patched, reconfigured, remake'd, remake install'd - but
> no change. however, some more likely helpful information below for
> you. Thank you
Odd. Are you sure that the new version of usbhid-ups got installed to the same path you are running? Also, there is no protection against
2020 Jan 01
2
Tripp Lite SMART1500LCD will not stay shut down when power is disconnected
...ature, ReportID:
0x10, Offset: 0, Size: 8, Value: 0
0.170429 Path: UPS.Flow.ConfigVoltage, Type: Feature, ReportID:
0x01, Offset: 0, Size: 8, Value: 120
0.172417 Path: UPS.Flow.ConfigFrequency, Type: Feature, ReportID:
0x02, Offset: 0, Size: 8, Value: 60
0.174421 Path: UPS.Flow.ConfigApparentPower, Type: Feature,
ReportID: 0x03, Offset: 0, Size: 16, Value: 1500
0.176420 Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown, Type:
Feature, ReportID: 0x15, Offset: 0, Size: 16, Value: 65535
0.178432 Path: UPS.OutletSystem.Outlet.ffff00bc, Type: Feature,
ReportID: 0xe0, Offset: 0, Size...
2017 Dec 20
3
Tripp-Lite BCPERS450 shutdown/restart problems
...st, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 0
0.065790 Path: UPS.Flow.ConfigVoltage, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 120
0.066320 Path: UPS.Flow.ConfigFrequency, Type: Feature, ReportID: 0x02, Offset: 0, Size: 8, Value: 60
0.066955 Path: UPS.Flow.ConfigApparentPower, Type: Feature, ReportID: 0x03, Offset: 0, Size: 16, Value: 450
0.067583 Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown, Type: Feature, ReportID: 0x15, Offset: 0, Size: 16, Value: 65535
0.068231 Path: UPS.OutletSystem.Outlet.ffff00bc, Type: Feature, ReportID: 0xe0, Offset: 0, Size: 16, Val...
2006 Nov 15
1
Tripp Lite OMNI900LCD
...tery.PresentStatus., Type: Feature
Path: UPS.BatterySystem.Battery.PresentStatus., Type: Feature
Path: UPS.BatterySystem.Test, Type: Feature, Value: 0.000000
Path: UPS.Flow.ConfigVoltage, Type: Feature, Value: 120.000000
Path: UPS.Flow.ConfigFrequency, Type: Feature, Value: 60.000000
Path: UPS.Flow.ConfigApparentPower, Type: Feature, Value: 900.000000
Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown, Type: Feature, Value: 65535.000000
Path: UPS.OutletSystem.Outlet.ffff0091, Type: Feature, Value: 0.000000
Path: UPS.OutletSystem.Outlet.ffff0092, Type: Feature, Value: 0.000000
Path: UPS.OutletSystem.Outlet.ffff00c...
2020 Jun 28
2
AVR750U Low Power not Triggering Shutdown
...e: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 120
0.044002 Path: UPS.Flow.ConfigFrequency, Type: Feature, ReportID: 0x02, Offset: 0, Size: 8, Value: 60
0.045016 Path: UPS.Flow.ffff0097, Type: Feature, ReportID: 0x55, Offset: 0, Size: 8, Value: 2
0.046012 Path: UPS.Flow.ConfigApparentPower, Type: Feature, ReportID: 0x03, Offset: 0, Size: 16, Value: 750
0.047000 Path: UPS.PowerConverter.Input.Voltage, Type: Feature, ReportID: 0x18, Offset: 0, Size: 16, Value: 0.001233