Citeren Benjamin Hase <benjamin.hase at googlemail.com>:
> just want to report a successful installation of the Digitus DN-170020
> UPS.
Thanks for reporting this, we appreciate feedback like this to keep
our list of supported devices current.
> Works mostly without problems with the megatec driver and the
> included cable, a few issues arose:
>
> - the toggle beeper command seems not to work for this UPS.
This is a known problem that is mentioned in the manual page 'man 8
megatec'.
> - to shutdown and cut the power line, a delay has to be inserted for
> the driver; without the UPS just beeps but does not switch off.
I'm not quite sure I understand what you mean here. Where did you add
this delay?
> - the test commands do not work for this UPS.
Known problem too. Many vendors use this protocol (or something that
is similar enough to be understood by the megatec driver) without
fully implementing it.
> I think, these problems are based on firmware flaws.
Yes.
> What works so far:
> - reporting of power failure
> - automated shutdown (tested with upsmon -c fsd)
> - automatic restart (after the two minutes set in config file, not
> tested with real power cut)
If you would have added the output of 'upsc' too, you would be the
winner of our grand prize today. :-)
> What is unknown:
> - accuracy of sensor values (temperature, voltage, frequency and so on)
'A UPS is not a measurement instrument' (tm)
> As long as the UPS reports its critical state early enough, I don't
> bother about the sensor values ;-)
Indeed.
> If in need, I can post my config files, too.
The config files are not needed, but it would be nice to see:
- the output of 'upsc'
- what you did to make the UPS shutdown
If you can send this, I'll add it to the list of supported devices.
Best regards, Arjen
--