similar to: Unconventional Setup

Displaying 20 results from an estimated 8000 matches similar to: "Unconventional Setup"

2024 Feb 21
1
System keeps going into FSD mode after power on
Hello, I am a new user of NUT and trying to wrap my ahead around a couple of things. I installed NUT 2.7.4-13 from package on RasPi 4, running Raspbian Linux 11 (bullseye). I have Cyberpower SL700U connected to it. For testing I set battery.charge.low to 90, so I wouldn't have to wait a long time. See all relevant config below. First of all, what seems to happen is that UPS gets to the low
2015 Sep 11
3
"upsmon -c fsd" cause system shutdown
hi: my testing server has two power supply and attach to two ups. one of the ups is connect to the server with usb. my upsmon.conf like below: # for two ups MONITOR ftups at localhost 1 monmaster nutmaster master MONITOR ftups at 10.1.1.2 1 monslave nutslave slave MINSUPPLIES 1 # for early shutdown NOTIFYFLAG ONBATT EXEC+WALL+SYSLOG NOTIFYFLAG ONLINE EXEC+WALL+SYSLOG NOTIFYCMD
2023 Oct 31
1
FSD sequence: Waiting for bigger and slower clients before cutting power
fredag 27 oktober 2023 20:07:58 CET skrev Jim Klimov: > Hi, this does sound like a useful idea - although for the principle of > least surprise and for variation in deployments, I'd rather have it as a > (non-default state of a) configuration toggle that can be set via > `upsmon.conf`: whether this particular client exits after processing FSD or > not. The onus for the rest
2012 Jan 06
1
upsmon+snmp-ups does not shut down system
I've googled and RTFM'ed, but still can't solve this one. I hope you folks can. This affects my entire computer cluster, but let's start simple: I've got a computer running NUT; OS is Scientific Linux 5.5; kernel 2.6.18-274.12.1.el5xen. It connects to an APC SMART-UPS via an APC SmartCard using the snmp-ups driver. It generally works: upsmon will detect if the battery is low
2020 Aug 14
4
Synology NAS is shutting down Ubuntu servers after very brief power outage (fwd)
Thanks Larry, no problem. I appreciate the input. Whenever you get a chance I’d really like to compare notes with someone who has NUT and a Synology to see why the heck mine doesn’t work! ;). I’m also using my Pi as the master like you. Thanks. Todd -- Todd Benivegna // todd at benivegna.com On Aug 14, 2020, 11:55 AM -0400, Larry Fahnoe <fahnoe at fahnoetech.com>, wrote: > On Fri, Aug
2023 Oct 27
2
FSD sequence: Waiting for bigger and slower clients before cutting power
Hi, this does sound like a useful idea - although for the principle of least surprise and for variation in deployments, I'd rather have it as a (non-default state of a) configuration toggle that can be set via `upsmon.conf`: whether this particular client exits after processing FSD or not. The onus for the rest would be on general systems integration - e.g. ensure that init scripts `K*`ill the
2012 Feb 28
2
NUT driver update process...
Hi Billy, switching back this thread to -upsdev 2012/2/27 William R. Elliot <bill at wreassoc.com>: > I have been able to set the 'FSD' from the driver and it is picked up by > upsmon.? That gives me the functionality that I was asked to put in the > driver.? If that is against the rules then I'll make an adjustment when the > allowed method is defined.? :-) yup,
2013 Sep 11
1
Issue with slave FSD notification on Windows port of NUT
I have the latest version of the Windows port of NUT installed on my Windows?7?machine. The UPS is connected via serial cable to the Windows machine. I also have my Synology NAS (which uses NUT) connected over the local network as a slave to the Windows NUT master. The Synology slave is configured to immediately go into "safe mode" whenever an FSD or OB+LB indication is received from the
2020 Aug 14
1
Synology NAS is shutting down Ubuntu servers after very brief power outage (fwd)
On Fri, 14 Aug 2020, Todd Benivegna wrote: > https://forum.synology.com/enu/viewtopic.php?f=19&t=73960&hilit=ups+slave  > > I have the latest version of the Windows port of NUT (A UPS management package) installed on my Windows 7 machine. The UPS I am using is a > very old APC BK650M which is controlled and sends its status via a special serial cable to the Windows
2020 Jan 11
4
System with MGE UPS shuts down too early
Hello, I'm experiencing a strange early shutdown behavior with the following system: * */OS/*: Slackware Linux 14.2 x86_64 * */NUT/*: 2.7.4 (from my own package <https://sotirov-bg.net/slackpack/pack.cgi?id=4083>) * */UPS/*: MGE Ellipse PRO 1600 <powerquality.eaton.com/Products-services/Backup-Power-UPS/Ellipse-PRO.aspx> (bought in September 2017) */Problem
2006 Aug 17
1
powercom issues
And something else, that previously eluded from my thoughts:my "notifyme" script,i.e the script that is executed at an ups.status="OB" event, is: echo `date` >> /root/upsLog echo " No power, shutting down the system!" >> /root/upsLog sleep 30 control=`/usr/local/ups/bin/upsc Inform@localhost ups.status` if [ $control != OL ] then
2015 Oct 28
5
The system doesn't shutdown
> > Did you see a line in the journal similar to this ? > Oct 06 22:49:54 pinta nut-delayed-ups-shutdown[1854]: > nut-delayed-ups-shudown.service calling > upsdrvctl to shut down UPS unit Never after I disabled the service. I pasted the whole journal section of the successful shutdown from last email. However I have been thinking about this line
2023 Oct 27
2
FSD sequence: Waiting for bigger and slower clients before cutting power
Hi, and thanks for this great piece of free software! I've been meaning to sort this out for some time, but we don't get power outages that often, fortunately... So, correct me if I'm wrong, but from the documentation at https:// networkupstools.org/docs/user-manual.chunked/ Configuration_notes.html#UPS_shutdown, and also reading upsmon.c, when a UPS goes OB LB (assuming we have a
2015 Feb 09
2
About your driver NUTDRV_ATCL_USB(8) for install
On Feb 9, 2015, at 6:48 AM, PERE (yahoo.es) <pererivers at yahoo.es> wrote: > 0.028188 Can't set USB configuration: could not set config 1: Device or resource busy > 0.029246 detached kernel driver from USB device... > 0.030559 USB device [0001:0000] opened > 0.866216 read: (8 bytes) => 03 00 00 00 00 00 00 00 > 0.866413 reply[0] = 0x03
2007 Jan 31
5
Additional server eralier shutdown condition
Is it possible to shutdown earlier by certain conditions: by battery level and estimated by UPS runtime. In APCUPSD this done by config options "BATTERYLEVEL" "MINUTES". By what condition NUT shutdown server? How to disable UPS shutdown?
2020 Sep 29
5
Question about hardware failures / FSD
Hello, The UPS I am developing a driver to is able to report several flags for critical hardware conditions, like overheat, overload, inverter failure, output short etc. What should be the correct policy of operation when such a condition occurs? I think that the an UPS in such a condition is not reliable and therefore a system shutdown should be called. However, the developer's manual and
2020 Jun 28
2
AVR750U Low Power not Triggering Shutdown
Thanks for the quick response! On Sat, Jun 27, 2020, at 22:17, Manuel Wolfshant wrote: > On 6/28/20 4:25 AM, Scott Colby wrote: > > Hello, > > > > I am having difficulty using NUT to shut down my Netgate SG-1100 > > (a pfSense router) when the power level of the UPS gets critically > > low. > > > > Here is some relevant information: > > - OS:
2012 Mar 08
18
some fixes, improvements, and new features (EPO and DYING) for NUT
Here are a series of my recent changes to NUT. The first few in the set are primarily little fixes and improvements. In among those are a few for .gitignore files which of course you can ignore for SVN, and there's one for a commit to a generated file which of course should not be tracked in any VCS. Then there are a couple or three to do with generating the header files used by
2020 Jan 24
2
System with MGE UPS shuts down too early
On January 24, 2020 6:13:31 PM GMT+02:00, "Georgi D. Sotirov" <gdsotirov at gmail.com> wrote: >OK, my UPS turned out to be older that I thought. I apparently bought >and installed it in September 2016 (not 2017 as I initially wrote). >That >makes for over 3 years of work, which is over the life expectancy of >the >batteries, Good batteries can last 4-5 years.
2022 Mar 11
2
On retiring some terminology
FYI: PR https://github.com/networkupstools/nut/pull/1328 adds handling of `PRIMARY` alias to `MASTER` on protocol side, hopefully completing the puzzle for issue #840. Reviews and testing would be welcome :) On Sun, Mar 14, 2021, 00:34 Jim Klimov <jimklimov+nut at gmail.com> wrote: > Thanks again for all the suggestions. > > For now I've prepared draft PRs, mostly to map out