similar to: New UPS ABB

Displaying 20 results from an estimated 100 matches similar to: "New UPS ABB"

2014 Jan 21
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote: > MONITOR UPS_251 at localhost 2 monmaster password master > MONITOR UPS_252 at localhost 2 monmaster password master I think the "2"s here should be "1". "powervalue is an integer representing the number of power supplies that the UPS feeds *on this system*." So if UPS_251 is connected to one power supply on
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
I tried all options: 1,2 and in MINSUPPLIES: 1,2,3,4 still didn't work. UPS_251 and UPS_252 feeds all environment and it's not feed directly one server, but many of them. > On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote: > >> MONITOR UPS_251 at localhost 2 monmaster password master >> MONITOR UPS_252 at localhost 2 monmaster password master > > I think the
2014 Jan 21
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote: > It does not matter what value I'll put in MONITOR and MINSUPPLIES line. NUT not waiting for both UPS to start timer. Correct. You can think of upssched as operating on raw UPS status, rather than the calculated powervalue that upsmon uses to decide when to shut down. -- Charles Lepple clepple at gmail
2016 Oct 25
2
setting up CYBERPOWER CP1500PFCLCD
Hi, Another beginner question. I spend hours trying to find the solution for how to configure winnut properly but I' struggling to make it work. I want my QNAP NAS TS-231 to work as a master and send signal to the PC to shut it down during power outage. I configured QNAP properly (like this: http://geekbeat.tv/qnap-adding-external-devices-qnap), but I don't know what to do next. I work
2017 Jan 09
2
NUT Client shuts down when performing runtime calibration on APC UPS
Here are the results from the output of upsc under different conditions from my Debian Test system with NUT 2.7.2 : Normal: ups.status: OL No wall power: ups.status: OB Runtime calibration (started from AP9630 web interface): ups.status: OB CAL So at this stage there is a difference! I then connected to my QNAP and set the UPS settings on the web interface to "Shutdown server if power
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
So it's impossible to configure upssched to start timer only if all ups are in status: OB or LB ? > On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote: > >> It does not matter what value I'll put in MONITOR and MINSUPPLIES line. >> NUT not waiting for both UPS to start timer. > > Correct. You can think of upssched as operating on raw UPS status, rather > than the
2016 Oct 26
0
setting up CYBERPOWER CP1500PFCLCD
[please use reply-all to include the list - the headers are not mangled] On Oct 25, 2016, at 9:53 AM, Tomasz Przychodzie? wrote: > > Hi, > > Another beginner question. I spend hours trying to find the solution for how to configure winnut properly but I' struggling to make it work. I want my QNAP NAS TS-231 to work as a master and send signal to the PC to shut it down during
2007 Feb 07
1
Network Management Card (MGE) 66102 with snmp-ups
I'm trying to set up nut with a MGE UPS equiupped with a network management card, but encountered a problem. UPS: MGE Pulsar M 3000 Network Management card (installed in the UPS): 66102 (2006 edition) Operating system: FreeBSD Nut port version: 2.0.5 Nut driver: snmp-ups According to MGE in Norway this card is supported by nut, but only the old version of the card (66244) is listed on
2016 Oct 26
2
setting up CYBERPOWER CP1500PFCLCD
I changed IP to NAS IP instead of my PC IP and also used NAS login and pass. Didn't work. When I wanted to launch WinNUT with new settings I got: "Fatal error: insufficient power configured!" (same as before) I got this log: Level INFO 10/26/2016 10:46:17 Detected OS as Windows NT Level NOTICE 10/26/2016 10:46:17 Network UPS Tools upsmon 2.0.0.4 Level INFO
2019 Oct 08
0
APC AP9630 SNMP AES
Hello, i'm trying to monitor a APC Smart-UPS 1000 behind a APC AP9630 Network Management Card via SNMPv3 using the AES Privacy Protocol. * OS name and version: Debian 10.1 * exact NUT version: 2.7.4 * NUT installation method: from debian package 2.7.4-8 * exact device name and related information * Model Number AP9630 * Hardware Revision 08 * Manufacture Date
2019 Oct 11
0
NUT-DRIVER cant start [Emerson Liebert APM 150 kVA]
Hi, I'm trying connect a device: * OS name and version: root at nut:/etc/nut# hostnamectl Static hostname: nut Icon name: computer-vm Chassis: vm Machine ID: d7a3b7fc724f4fe1a79a3d0eeff08f72 Boot ID: 40a561c464064b5184150f5909af0aa7 Virtualization: vmware Operating System: Debian GNU/Linux 9 (stretch) Kernel: Linux 4.9.0-9-amd64 Architecture: x86-64 * NUT version
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
> What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines when to shut down. > > Also, if you don't want to wait for both UPSes to drain to the low battery state, you can set up a pair of dummy-ups drivers. I'm
2014 Jan 21
3
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 3:16 AM, Rafa? Oleszek wrote: > I would like to mention that MINSUPPLIES manipulation doesn't work. My nut version is : 2.2.2-4 (RHEL 5) What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines
2006 Feb 07
1
MGE Pulsar STS
Hello, I'm trying to communicate with a MGE Pulsar STS 16 using nut under Linux, but I've had no luck so far. I haven't saw it supported in the doc, so if there's anything I can try... Thanks, Arnaud. -- Perso: http://launay.org/blog/ H?bergement: http://www.nocworld.com/
2016 May 18
1
Monitoring Only
Hi, What shoud I do in order to configure NUT to perform only monitoring, I mean to not shutdown anything at all? Thanks in advance! -- -- Sergio Belkin LPIC-2 Certified - http://www.lpi.org -------------- next part -------------- An HTML attachment was scrubbed... URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20160518/23c72ff1/attachment.html>
2014 Jan 23
0
Shutdown when both (all) UPS on battery / low battery
> On Jan 21, 2014, at 9:24 AM, Rafal Oleszek wrote: > >> I tried all options: >> 1,2 >> and in MINSUPPLIES: 1,2,3,4 >> still didn't work. > > My mistake - I gave you the wrong advice before. For MINSUPPLIES, I'm used > to either a 1:1 UPS-to-server ratio, or 2:1 where the server can run with > either power supply unpowered. > > I just tried
2008 May 01
1
NUT for laptop
HI all How to setup nut to use and monitor laptop battery on linux? (/proc/acpi/battery/BAT0/state) Emard
2014 Jan 23
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 9:24 AM, Rafal Oleszek wrote: > I tried all options: > 1,2 > and in MINSUPPLIES: 1,2,3,4 > still didn't work. My mistake - I gave you the wrong advice before. For MINSUPPLIES, I'm used to either a 1:1 UPS-to-server ratio, or 2:1 where the server can run with either power supply unpowered. I just tried this in upsmon.conf: MONITOR dummy1 1 monuser
2006 Nov 07
6
Sweex 1000VA UPS
Hi, I'm trying to get a sweex ups working with nut on debian sarge. This one: http://www.sweex.com/producten.php?lang=1&%20sectie=&item=59&artikel=95 It's shipped with UPSmart and according to the compatibility list it should work with the genericups upstype=7 driver. But it doesn't. I get: mybox:/etc/nut# /etc/init.d/nut start Starting Network UPS Tools: (upsdrvctl
2010 Jul 30
4
Concept questions: Extra battery packs & additional UPSes...
* Is there a way to configure NUT so that it recognizes the huge additional battery pack that has been attached to the 2200XL? The 51minutes runtime is a number consistent with the load we have placed on a stock standalone 2200XL. With the extra large battery pack we've added, the runtime should be more than 2.5 hours. * I see the "Bizzare configuration" graphic on the