2018 Jul 01
0
No run cmd /usbhid-ups -k !
On 01/07/2018 11.53, icingaj at gmail.com wrote: > Good day. > > Can not perform shutdowns Ups. Please help. > > Details of our installation are: > OS: Turris Omnia (TO) > NUT version: 2.7.4-5 > Installation method: from package > UPS device: EATON UPS 5SC 500i , 230V, 350W, 500VA, USB bought in jun 2018 > > If you connect to TO UPS via USB, the /dev/hidraw0
2018 Jul 02
4
No run cmd /usbhid-ups -k !
I used strace and the result is bus is busy: clock_gettime(CLOCK_MONOTONIC, {8158, 708518222}) = 0 timerfd_settime(11, TFD_TIMER_ABSTIME, {it_interval={0, 0}, it_value={8159, 708518000}}, NULL) = 0 ioctl(12, USBDEVFS_SUBMITURB, 0x40810) = 0 poll([{fd=7, events=POLLIN}, {fd=9, events=POLLIN}, {fd=11, events=POLLIN}, {fd=12, events=POLLOUT}], 4, 60000) = 1 ([{fd=12, revents=POLLOUT}]) ioctl(12,
2018 Jul 03
2
No run cmd /usbhid-ups -k !
Hi all. UPS is Eaton 5SC 500i. I tested three solutions: 1. swap "usbhid-ups -a qnapups" with "usbhid-ups -a qnapups -k" Result: server shutdown, but ups does not shut off! 2. run prog with params "upsmon -c fsd" Result: server shutdown, but ups does not shut off! 3. run prog "upscmd -u name -p passwd qnapups shutdown.return" and next
2013 Sep 12
3
UPS repeater configuration using localhost
Hello, I'm trying to setup a UPS configuration whereas I have one physical UPS but two UPS entities loaded by the system used by different network slaves. In my ups.conf configuration I have ... [ups] driver = apcsmart port = /dev/ttyS0 desc = "APC UPS" [qnapups] driver = dummy-ups port = ups at localhost desc = "APC UPS for
2018 Jul 03
1
No run cmd /usbhid-ups -k !
Set with upsrw: ups.delay.shutdown=60 is the same as offdelay = 30. This time was done correctly by UPS. Set with upsrw: ups.delay.start=90 is the same as ondelay = 40. The UPS shut down and reset and forget about the settings. If I use the program in Win 10 settings in the program from Eaton are stable!? Jan. > -----Original Message----- > From: Nut-upsuser
2013 Sep 16
0
UPS repeater configuration using localhost
On Sep 12, 2013, at 7:47 PM, Derek Rachul <drachul at gmail.com> wrote: > I tried reversing the order of the definitions in the config file, and it does seem to change the order in which they're loaded (at least according to the system logs) however the error remains. I don't have any experience using the dummy-ups driver on the same host as the real UPS driver, so this is a
2023 Jan 12
1
NUT & UPS, how to shut down client after 2 min on battery?
Now I have this in /etc/nut/upsmon.conf (my QNAP NAS wants admin and 123456 or not working) RUN_AS_USER root MONITOR qnapups at localhost 1 admin 123456 master MONITOR qnapups at 192.168.222.252 3493 admin 123456 slave MINSUPPLIES 1 SHUTDOWNCMD "/sbin/shutdown -h +0" POLLFREQ 5 POLLFREQALERT 5 HOSTSYNC 15 DEADTIME 15 POWERDOWNFLAG /etc/killpower NOTIFYFLAG ONLINE SYSLOG+EXEC
2011 Jan 14
6
Plexus UPS on a QNAP NAS
Hi, Has anyone managed to get a Plexus UPS talking to their NAS. I've followed the excellent instructions here http://forum.qnap.com/viewtopic.php?f=182 <http://forum.qnap.com/viewtopic.php?f=182&t=35970&start=0> &t=35970&start=0 but I'm not there yet. When I manually start upsdrvctl without the UPS plugged in I get [~] # /usr/bin/upsdrvctl start Network UPS
2022 Dec 22
3
NUT & UPS, how to shut down client after 2 min on battery?
Hi! Some systems I have take some time to shut down, so I would like them to shut down if the UPS have been on battery for 2 minutes. Internet has told me that SHUTDOWNCMD ?/sbin/shutdown -h +0? in /etc/nut/upsmon.conf will execute when the UPS is both OB (on battery) and LB (Low battery). Like in wiki.ipfire.org - Detailed NUT Configuration<https://wiki.ipfire.org/addons/nut/detailed>
2016 Oct 25
2
setting up CYBERPOWER CP1500PFCLCD
Hi, Another beginner question. I spend hours trying to find the solution for how to configure winnut properly but I' struggling to make it work. I want my QNAP NAS TS-231 to work as a master and send signal to the PC to shut it down during power outage. I configured QNAP properly (like this: http://geekbeat.tv/qnap-adding-external-devices-qnap), but I don't know what to do next. I work
2021 Nov 16
1
nut proxy setup?
I've searched for quite some time and read the FAQ, but to no avail. I have a UPS connected to a NAS. Unfortunately I have to specify every single client IP (ups slave), because the stupid NAS system (QNAP) does not allow me to set a /16 or /24. Changing the config files manually does not work either, because the service won't come up anymore. (One has to love QNAP at this point.) Thus I
2013 Sep 17
0
UPS repeater configuration using localhost
[please keep the list CC'd. Thanks!] On Sep 16, 2013, at 8:11 PM, Derek Rachul <drachul at gmail.com> wrote: > On Mon, Sep 16, 2013 at 4:36 PM, Charles Lepple <clepple at gmail.com> wrote: >> On Sep 12, 2013, at 7:47 PM, Derek Rachul <drachul at gmail.com> wrote: >> >> > I tried reversing the order of the definitions in the config file, and it does
2018 Jul 02
0
No run cmd /usbhid-ups -k !
Sorry i forgot send info from: # /lib/nut/usbhid-ups -DD -x explore -a qnapups &> usbhid-ups.debug.log Thx Jan. -------------- next part -------------- A non-text attachment was scrubbed... Name: usbhid-ups.debug.log Type: application/octet-stream Size: 23064 bytes Desc: not available URL:
2010 Nov 07
3
Support of "shutdown.return" on a APC Back-UPS CS 500
Hi all, I am trying to get a APC Back-UPS CS 500 running on my QNAP 419P Nas. Since on all my work I figure out the following: from Network UPS Tools upscmd 2.4.1 [~] # upscmd -l qnapups Instant commands supported on UPS [qnapups]: beeper.disable - Disable the UPS beeper beeper.enable - Enable the UPS beeper beeper.mute - Temporarily mute the UPS beeper beeper.off - Obsolete (use
2016 Oct 26
0
setting up CYBERPOWER CP1500PFCLCD
[please use reply-all to include the list - the headers are not mangled] On Oct 25, 2016, at 9:53 AM, Tomasz Przychodzie? wrote: > > Hi, > > Another beginner question. I spend hours trying to find the solution for how to configure winnut properly but I' struggling to make it work. I want my QNAP NAS TS-231 to work as a master and send signal to the PC to shut it down during
2014 Jul 09
0
Documenting the NUT driver-qualification process
On Jul 9, 2014, at 6:31 AM, Eric S. Raymond <esr at thyrsus.com> wrote: > What I'd like to do is this: confer in real-time, perhaps via IRC, > with someone who knows this process. Ask about every step (thought > processes and diagnostics). *Write them down* and turn this into a > document on how to qualify and support a new device. Happy to help, but scheduling something
2009 Oct 06
1
Powerware USB issue solved (bcmxcp_usb)
Hi Greg, Thomas and the list, I've not forgotten you nor your issue. It just took some time to gather a "faulty" unit and a bit of time to reproduce your issue. The good news is that I've commited a fix to the NUT development branch (aka Subversion), in the release r2015. The bad news is that your test and feedback is welcome ;-) For more info on getting and compiling the
2018 Jul 03
0
No run cmd /usbhid-ups -k !
On Tue, 3 Jul 2018, rakoi at mail.telekom.sk wrote: > UPS is Eaton 5SC 500i. > Please do not know how to write some parameters permanently to UPS? Read man ups.conf and man usbhid-ups and try setting the required values in ups.conf. For example [Eaton] driver = usbhid-ups port = auto desc = "Eaton 5sc 500i" offdelay = 30 ondelay =
2009 Jul 02
1
Hardware donation - 7600 GS (AGP)
Are there any Nouveau developers in Europe (preferably in the UK) who would like a GeForce 7600 GS? It's the AGP version and is no longer useful to me. I've got the power dongle (it requires a 350W power supply) and a S-Video to composite dongle. Specs: BFG GeForce 7600 GS OC (AGP) 512MB RAM DVI + VGA 1 x power dongle (the sort that plug into pata drives) 1 x "HDTV" dongle
2017 Jan 09
2
NUT Client shuts down when performing runtime calibration on APC UPS
Here are the results from the output of upsc under different conditions from my Debian Test system with NUT 2.7.2 : Normal: ups.status: OL No wall power: ups.status: OB Runtime calibration (started from AP9630 web interface): ups.status: OB CAL So at this stage there is a difference! I then connected to my QNAP and set the UPS settings on the web interface to "Shutdown server if power