Displaying 20 results from an estimated 4000 matches similar to: "how to use multiple UPS with timers"
2018 May 09
1
how to use multiple UPS with timers
Yes both UPS units are on different power supplies. MINSUPPLIES is set to 1.
Afaik NUT waits for OB and LB before shutting down the system. Is there a way to change this behavior to only wait for OB?
Then I would use FINALDELAY in case the power outage doesn't last long.
I already tried to change the battery.runtime.low setting over the webinterface of the CS121 (snmp is readonly) but with
2014 Jan 23
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 9:24 AM, Rafal Oleszek wrote:
> I tried all options:
> 1,2
> and in MINSUPPLIES: 1,2,3,4
> still didn't work.
My mistake - I gave you the wrong advice before. For MINSUPPLIES, I'm used to either a 1:1 UPS-to-server ratio, or 2:1 where the server can run with either power supply unpowered.
I just tried this in upsmon.conf:
MONITOR dummy1 1 monuser
2014 Jan 23
0
Shutdown when both (all) UPS on battery / low battery
> On Jan 21, 2014, at 9:24 AM, Rafal Oleszek wrote:
>
>> I tried all options:
>> 1,2
>> and in MINSUPPLIES: 1,2,3,4
>> still didn't work.
>
> My mistake - I gave you the wrong advice before. For MINSUPPLIES, I'm used
> to either a 1:1 UPS-to-server ratio, or 2:1 where the server can run with
> either power supply unpowered.
>
> I just tried
2018 May 08
0
how to use multiple UPS with timers
On Tue, 2018-05-08 at 11:27:45 +0000, Pilch, Alexander wrote:
> Hi,
>
> I need to shut down a VMWare host if both connected UPS are x minutes on battery. Both UPS are connected via SNMP.
> Because there are multiple vm running on that host, shutting every vm down takes some time. So most likely, waiting for low battery, the time left won't be enough. I tried overwriting the
2018 May 08
0
how to use multiple UPS with timers
On Tue, 8 May 2018, Pilch, Alexander wrote:
> I need to shut down a VMWare host if both connected UPS are x minutes on battery.
If these two UPS units are on different power supplies then it is possible for
one to reach x minutes on battery while the other is still on wall power.
> Are timers the only possible solution to this problem?
NUT provides the MINSUPPLIES declaration in
2005 Sep 13
3
timers and their usage
Hi everyone,
new to the list but a long time nut user.
I've tried a couple of times to set up a timer to avoid getting annoying
messages when the system goes on battery for only a few seconds.
in uppsched.conf I added this at the bottom:
AT ONBATT * START-TIMER onbattwarn 60
AT ONLINE * CANCEL-TIMER onbattwarn
What am I missing? it still doesn't wait before alerting me.
2014 Jan 21
3
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 3:16 AM, Rafa? Oleszek wrote:
> I would like to mention that MINSUPPLIES manipulation doesn't work. My nut version is : 2.2.2-4 (RHEL 5)
What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines
2005 Jul 28
2
lattice/ grid.layout/ multiple graphs per page
Background:
OS: Linux Mandrake 10.1
release: R 2.0.0
editor: GNU Emacs 21.3.2
front-end: ESS 5.2.3
---------------------------------
Colleagues
I have a set of lattice plots, and want to plot 4 of them on the page.
I am having trouble with the layout.
grid.newpage()
pushViewport(viewport(layout = grid.layout(2,2)))
pushviewport(viewport(layout.pos.col = 1, layout.pos.row = 1))
working trellis
2014 Jan 21
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote:
> MONITOR UPS_251 at localhost 2 monmaster password master
> MONITOR UPS_252 at localhost 2 monmaster password master
I think the "2"s here should be "1".
"powervalue is an integer representing the number of power supplies that the UPS feeds *on this system*."
So if UPS_251 is connected to one power supply on
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
I tried all options:
1,2
and in MINSUPPLIES: 1,2,3,4
still didn't work.
UPS_251 and UPS_252 feeds all environment and it's not feed directly one
server, but many of them.
> On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote:
>
>> MONITOR UPS_251 at localhost 2 monmaster password master
>> MONITOR UPS_252 at localhost 2 monmaster password master
>
> I think the
2015 Feb 09
2
About your driver NUTDRV_ATCL_USB(8) for install
On Feb 9, 2015, at 6:48 AM, PERE (yahoo.es) <pererivers at yahoo.es> wrote:
> 0.028188 Can't set USB configuration: could not set config 1: Device or resource busy
> 0.029246 detached kernel driver from USB device...
> 0.030559 USB device [0001:0000] opened
> 0.866216 read: (8 bytes) => 03 00 00 00 00 00 00 00
> 0.866413 reply[0] = 0x03
2020 Jan 01
2
Belkin USB UPS Not Turning Off
Well it is the season for storms and power outages here in the US PNW. I
noticed that today when the power went out, NUT mostly did what I
hoped/wanted. But it did not actually turn off the UPS at all. The UPS
kept beeping and I had to turn it off manually.
I thought that NUT would handle this. But perhaps it cannot for my unit?
Or perhaps I have things improperly configured? Any suggestions?
2017 Oct 19
1
debian 8 "jessie" nut 2.7.2 slaves not shutting down
Roger,
The topology is:
UPS TOPAPC, Data link to master, Power supply to master, slave1 and slave2
UPS MIDAPC, Data link to master, Power supply to master, slave1 and slave2
UPS BOTAPC, Data link to master, Power supply to master, slave1 and slave2
Shutdown plan:
When wall power fails for any of the three UPS units, they continue powering the master and the two slaves. When two of the UPS
2012 Jan 04
3
NUT Windows port questions
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20120104/34be491b/attachment.html>
2014 Jan 21
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote:
> It does not matter what value I'll put in MONITOR and MINSUPPLIES line. NUT not waiting for both UPS to start timer.
Correct. You can think of upssched as operating on raw UPS status, rather than the calculated powervalue that upsmon uses to decide when to shut down.
--
Charles Lepple
clepple at gmail
2015 Feb 09
0
About your driver NUTDRV_ATCL_USB(8) for install
Dear Chales,
Thanks for your quick reply.
I have Raspberry with last Kernel [Linux pi1 3.18.6+ #753 PREEMPT Sun Feb 8
14:47:22 GMT 2015 armv6l GNU/Linux]
If <upsdrvctl>, <upsd> and <upsmon> are stopped <nutdrv_atcl_usb> Works well
without any error as "Device or resource busy".
If I run <upsc> command never receive any value from my ups <upsc
ups at
2011 Mar 15
1
Driver for AEG UPS
Hallo,
I'm loocking for a driver to connect a AEG UPS Protection A 1500 mit
nut.
The Error-massage is this:
Network UPS Tools - UPS driver controller 2.6.0
Network UPS Tools - Generic HID driver 0.35 (2.6.0)
USB communication driver 0.31
This Liebert device (06da:0003) is not (or perhaps not yet) supported
by usbhid-ups. Please make sure you have an up-to-date version of NUT.
If
this does not
2006 Aug 16
5
Master privileges unavailable on UPS, no access :(
Hello!
After I type "upsmon", in syslog the following message appears:
Aug 16 14:11:09 marto upsmon[7731]: Master privileges unavailable on UPS [Inform@localhost]
Aug 16 14:11:09 marto upsmon[7731]: Reason: Access denied
Can you tell me where my error is, my configuration files are:
ups.conf:
[Inform]
driver = powercom
port = /dev/ttyS0
desc = "inform guard"
linevoltage = 220
2016 Oct 26
2
setting up CYBERPOWER CP1500PFCLCD
I changed IP to NAS IP instead of my PC IP and also used NAS login and
pass. Didn't work. When I wanted to launch WinNUT with new settings I got:
"Fatal error: insufficient power configured!" (same as before)
I got this log:
Level INFO 10/26/2016 10:46:17 Detected OS as Windows NT
Level NOTICE 10/26/2016 10:46:17 Network UPS Tools upsmon 2.0.0.4
Level INFO
2012 Jan 28
2
No shutdown on empty battery
Hello,
I set up a FreeBSD 8.2 system with nut 2.6.1 and a Powerware 5115
connected by RS-232. I expected this setup to shut down before running
out of battery power, but I either missed some important configuration
or something else went wrong:
The syslog says:
Jan 9 05:03:42 b1 upsmon[67752]: UPS upsb1 at localhost on battery
Jan 9 05:04:42 b1 upsmon[67752]: UPS upsb1 at localhost on line