Displaying 20 results from an estimated 900 matches similar to: "APC Back-UPS XS 1500G says "No battery""
2009 Mar 13
7
Weird Load and Battery Temp Readings
I've acquired and installed NUT 2.4.1 on a D-Link DNS323 NAS. With
exception of Load and Battery Temp readings all works well. A upsc
ups at localhost command returns;
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 50
battery.date: 2001/09/25
battery.mfr.date: 2008/06/05
battery.runtime: 2122
battery.runtime.low: 120
battery.temperature: 3022999999999998800
battery.type:
2014 Oct 06
1
Return on experience with an Emerson/Liebert GXT3
Hi
On 10/03/2014 03:42 PM, Charles Lepple wrote:> On Oct 3, 2014, at 7:50 AM, paul.chavent at fnac.net wrote:
>
>
> This is what I was referring to (from the belkin-hid log):
>
>???? 1.325782??? Report[buf]: (5 bytes) => 05 53 00 48 00
>???? 1.325799??? Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x05, Offset: 16, Size: 16, Value: 0
>????
2009 Sep 20
2
TrippLite Eco Series UPS
I purchased a TrippLite ECO550UPS from Amazon a few days ago thinking
I was going to use it for my Windows Media Center HTPC. I've since
changed my mind and decided to use Mythbuntu but it I can't get my UPS
working with nut. I've tried all of the tripplite drivers and the
usbhid-ups driver. The tripplite_usb and usbhid_ups output is listed
below. The tripplite and tripplitesu drivers
2017 May 12
0
APC Back-UPS XS 1500G says "No battery"
On May 11, 2017, at 1:51 PM, Jesse Molina <jmolina at swoncology.net> wrote:
>
> I suspect this is a driver problem because while NUT claims the battery isn't plugged in, it's giving me battery runtime/charge info. Both can't be valid at the same time.
>
> I am at a remote location from the computer and UPS, so I can't physically go over and check. I asked a
2012 Mar 21
5
Socomec sicon Netys 2000 PR ups USb driver for ubuntu
Hello i tried to connect my netys 2000 pr ups to ubuntu 11.10 and i have a problem connecting it. After readin a few post i realized to dianosse the connection.
I need help resolving the connextion issue
So here is the response to??/lib/nut/usbhid-ups -u root -DDDDD -a netys:
Network UPS Tools - Generic HID driver 0.35 (2.6.1)
USB communication driver 0.31
? ?0.000000 ? ? send_to_all: SETINFO
2015 Mar 13
3
Problems with NUT 2.7.2 on CentOS 7 and using the Mini-Box OpenUPS
I?m a new user of NUT and the OpenUPS - in the past I?ve used APC hardware and apcupsd on Centos 6.
I?ve built NUT 2.7.2 from source but used the OpenUPS HID driver v0.4 that?s in github. I?m using firmware version 1.5 on the openups which is the latest published version; I?ve also tried 1.7 which Mini-box sent to me but reverted to the published version. Their support seems a bit slow!
I?ve got
2006 May 22
3
USB UPS and FreeBSD
I am looking at the newhid driver for this Pulsar EXtreme here but it gives
odd results, for example there is no status variable :)
eg
debug level is '2'
Checking device (0463/FFFF) (/dev/usb0//dev/ugen0)
- VendorID: 0463
- ProductID: ffff
- Manufacturer: unknown
- Product: unknown
- Serial Number: unknown
- Bus: /dev/usb0
Trying to match device
Device matches
HID descriptor retrieved
2014 May 29
2
Resetting replace battery status on Pulsar 1500
On 28 May 2014, at 21:59, Charles Lepple <clepple at gmail.com> wrote:
>> What would log it?
>
> The driver.
OK.
>> I could try running the driver with debugging and see if that shows anything of interest.
>
> That should help. Unfortunately for non-debug operation, it appears that most of the usbhid-ups instcmd messages are buried at debug level 3 or 5. That
2016 May 28
2
Powercom INF-800 support
Hello.
Not listed as supported, so here is some info,
[root at vhost ~]# /usr/sbin/usbhid-ups -DD -a powercom
Network UPS Tools - Generic HID driver 0.38 (2.7.2)
USB communication driver 0.32
0.000000 debug level is '2'
0.001318 upsdrv_initups...
0.074753 Checking device (0529/0001) (003/002)
0.074835 Failed to open device, skipping. (Permission denied)
2006 Sep 08
3
newhidups with APC Smart-UPS 1500
Hello,
I'm using the stable amd64 port of Debian Linux. I installed (the
latest) nut-2.0.1-4 and nut-usb packages for utilizing an APC Smart-UPS
1500 USB. I tried "apcupsd" first but "nut" makes an even more
sophisticated impression on me and has more security options.
I had problems with the newhidups driver. It didn't find a device with
matching VendorID. And
2005 Oct 02
3
more on 2.0.3-pre
Gentlemen,
I have now had a chance to run some initial tests of my changes to
apc-hid.c of the current development tree. Running newhipups and
inspecting the -DDDD output seems to indicate that with the fix below
everything seems to work as expected. However, I have not yet shut
my system in order to take the UPS out of action so that I can do my
various tests with a lightbulb load. I still hope
2006 Feb 08
2
2.0.3-pre2: Spurious UPS UPS@localhost battery is
Peter Selinger wrote:
> Hm. I need more information, as NUT seems to garble the values even
> before I can see them. I am not so worried about the date and
> temperatures (although, strangely, the battery replacement date
> appears to be Sept 25, 2001, which makes no sense). But the voltage is
> definitely important.
>
> [...]
>
Thanks Peter - I'll send the new
2015 Jan 09
0
persistent "low battery" condition
On Jan 8, 2015, at 11:43 PM, Graham Menhennitt <graham at menhennitt.com.au> wrote:
> Hello Nutters,
>
> I'm running nut 2.7.2 on FreeBSD 10-stable (via the FreeBSD port) with an APC Back-UPS CS 350 connected via USB. I get persistent (every few minutes) messages logged "battery is low" but I don't understand why. I don't think it's for the reason
2009 Sep 02
6
Selftest intervall, APC Smart-UPS 750 RM
Hello
I recently switched from apcupsd to NUT2.2.2 without
any troubles.
I tried to figure out how I can configure the self-test
intervall. The command upsrw lists only the variables
battery.charge.low
battery.runtime.low
ups.delay.shutdown
ups.delay.start
The command usbhid-ups -D and the listing under
http://obsvermes.org/cgi-bin/nut/upsstats.cgi?host=apcsmart at localhost&treemode
2006 Oct 18
2
newhidups with APC Smart-UPS 1500
I tested your fix (newhidups -DDD /dev/null) using both and APC Back-UPS
350 an APC Smart-UPS RT 2000 XL.
No more segmentation fault due to the fixed-size array.
~Jacob
-----Original Message-----
From: nut-upsdev-bounces@lists.alioth.debian.org
[mailto:nut-upsdev-bounces@lists.alioth.debian.org] On Behalf Of Peter
Selinger
Sent: Monday, October 16, 2006 12:12 PM
To: Schmier, Jacob
Cc: NUT
2015 Jan 09
2
persistent "low battery" condition
Hello Nutters,
I'm running nut 2.7.2 on FreeBSD 10-stable (via the FreeBSD port) with
an APC Back-UPS CS 350 connected via USB. I get persistent (every few
minutes) messages logged "battery is low" but I don't understand why. I
don't think it's for the reason described in the FAQ (but I'm not 100%
sure).
In the trace output I can see that
2019 Jun 11
2
UPS shuts down on NUT boot with low battery [APS Back-UPS RS 550G]
On Jun 10, 2019, at 2:32 PM, Marc Finns wrote:
>
> Hello, I read all FAQ and other sources but I could not find this situation, so I thought of asking the experts.
> I successfully configured a Raspberry NUT server to control my UPS that powers several devices (NUC with ESXI VMs, Synology NAS etc).
> All works well in principle, but I have the following behaviours that I could not
2010 Jul 12
2
LiebertPSP
Hi Guys
Having trouble getting my LiebertPSP UPS to work.
$ upsc upsname
battery.charge.low: 38
battery.charge.warning: 38
battery.type: PbAc
device.mfr: Emerson Network Power
device.model: LiebertPSP
device.serial:
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.vendorid: 10af
driver.version:
2016 Sep 11
4
How to get started (Windows)
> On Thu, 8 Sep 2016, Jeff Bowman wrote:
>
> > (Note: running
> > 'upsc ups at localhost' echoes only a blank line to the screen, as do
> > both 'upsmon' and 'upsd.')
>
> Something is wrong here. Is the daemon upsd running? On a Unix/Linux
> system, the command ps aux | grep ups gives the report
>
> upsd 3196 0.0 0.0 13228
2007 Jan 26
1
newhidups output for Geek Squad GS1285U
This took a long time because I had problems with my system. After I
reloaded my operating system several times I found I had a bad memory
module.
Here is the output from newhidups for my Geek Squad GS1285U. It just
kept repeating until I hit ctl-z. I think that this means nut will work
for this ups. My computer is not powered by the ups yet. I did not want
it to be powered down by accident.