2017 Mar 21
2
Is a timer a file?
On Tue, 21 Mar 2017, Arnaud Quette wrote:
> Hi Roger,
>
> reviving this discussion, since we have a Github ticket for 2.7.5:
> https://github.com/networkupstools/nut/issues/293
...
> I've made some additions to clarify things on the timer, and complete the script:
> https://github.com/networkupstools/nut/compare/upssched-doc?expand=1
Hi Arnaud, Your change to the
2019 Jun 08
2
How to shutdown macOS / mac OSX from Network UPS Tools client - NUT
Hi,
I’ve posted my question on Superuser.com but not had any replies in 2 weeks, so I guess no-one there knows anything about NUT.
https://superuser.com/questions/1441153/how-to-shutdown-macos-mac-osx-from-network-ups-tools-client-nut <https://superuser.com/questions/1441153/how-to-shutdown-macos-mac-osx-from-network-ups-tools-client-nut>
I’m looking for help in shutting down my iMac on
2024 Feb 21
1
System keeps going into FSD mode after power on
Hello,
I am a new user of NUT and trying to wrap my ahead around a couple of
things. I installed NUT 2.7.4-13 from package on RasPi 4, running Raspbian
Linux 11 (bullseye). I have Cyberpower SL700U connected to it. For testing
I set battery.charge.low to 90, so I wouldn't have to wait a long time. See
all relevant config below.
First of all, what seems to happen is that UPS gets to the low
2006 Mar 31
2
MGE UPS Comet EX RT 7 not setting LB
Hi,
I just got at work an MGE UPS Comet EX RT 7 and I can communicate fine
with it through mge-shut, it detects correctly when on battery.
I am using Nut 2.0.3 on Linux (RHEL 3).
I am trying to simulate a low battery condition to test my shutdown
procedure by setting lowbatt to 98%:
driver.parameter.lowbatt: 98
but the ups reaches this value, goes to 97% and still no LB.
I tried to change,
2020 Jan 01
2
Belkin USB UPS Not Turning Off
Well it is the season for storms and power outages here in the US PNW. I
noticed that today when the power went out, NUT mostly did what I
hoped/wanted. But it did not actually turn off the UPS at all. The UPS
kept beeping and I had to turn it off manually.
I thought that NUT would handle this. But perhaps it cannot for my unit?
Or perhaps I have things improperly configured? Any suggestions?
2020 Apr 23
3
Low battery unexpected shutdown
Hi, recently I observed that during a power outage, my NUT setup doesn't
shutdown properly. Indeed it never reaches the LowBattery state to notify
and initiate shutdown on clients. Reviewing my setup and logs I think I'm
facing multiple problems and I'm unable to point to real root cause.
First, let me focus on my scenario and current setup:
In normal status (ONLINE, fully charged)
2014 Jan 21
3
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 3:16 AM, Rafa? Oleszek wrote:
> I would like to mention that MINSUPPLIES manipulation doesn't work. My nut version is : 2.2.2-4 (RHEL 5)
What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines
2016 Jun 05
3
Is a timer a file?
On Sat, 4 Jun 2016, Charles Lepple wrote:
> On Jun 3, 2016, at 6:48 AM, Roger Price <roger at rogerprice.org> wrote:
>> ... the timer. I don't see it in /var/lib/ups where the locate tool
>> finds upsd.pid, and I don't see it in /run or /var/run where I see
>> upsmon.pid.
>>
> ... it seems that the timers are only stored in memory. See
>
2017 Mar 28
1
Is a timer a file?
Hi Arnaud,
On Wed, 22 Mar 2017, Arnaud Quette wrote:
> The technique is very general and is to send SIGUSR1/SIGUSR2 to the upsd daemon.? SIGUSR1 and SIGUSR2 are events just like ONBATT and ONLINE.
> The patch runs successfully on my opensuse 13.2 box, and solves my problem. In upssched.conf I now have declarations such as
>
> ? ?AT SIGUSR1 * CANCEL-TIMER
2019 Jun 08
3
How to shutdown macOS / mac OSX from Network UPS Tools client - NUT
On Jun 8, 2019, at 4:16 PM, Roger Price wrote:
>
> Is your System Shutdown Plan to shut down using upsmon or using the script upsched-cmd? In upssched.conf you do not have a line
>
> AT LOWBATT ups at ... EXECUTE lowbatt
>
> and in upssched-cmd there is nothing to shut down the system.
Joe,
Roger has a good point - the SHUTDOWNCMD should work as long as the master system
2022 Dec 22
3
NUT & UPS, how to shut down client after 2 min on battery?
Hi!
Some systems I have take some time to shut down, so I would like them to shut down if the UPS have been on battery for 2 minutes.
Internet has told me that SHUTDOWNCMD ?/sbin/shutdown -h +0? in /etc/nut/upsmon.conf will execute when the UPS is both OB (on battery) and LB (Low battery). Like in wiki.ipfire.org - Detailed NUT Configuration<https://wiki.ipfire.org/addons/nut/detailed>
2019 May 25
2
Low Battery False Alarms
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
> What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines when to shut down.
>
> Also, if you don't want to wait for both UPSes to drain to the low battery state, you can set up a pair of dummy-ups drivers. I'm
2020 Jan 11
4
System with MGE UPS shuts down too early
Hello,
I'm experiencing a strange early shutdown behavior with the following
system:
* */OS/*: Slackware Linux 14.2 x86_64
* */NUT/*: 2.7.4 (from my own package
<https://sotirov-bg.net/slackpack/pack.cgi?id=4083>)
* */UPS/*: MGE Ellipse PRO 1600
<powerquality.eaton.com/Products-services/Backup-Power-UPS/Ellipse-PRO.aspx>
(bought in September 2017)
*/Problem
2014 Jan 23
0
Shutdown when both (all) UPS on battery / low battery
> On Jan 21, 2014, at 9:24 AM, Rafal Oleszek wrote:
>
>> I tried all options:
>> 1,2
>> and in MINSUPPLIES: 1,2,3,4
>> still didn't work.
>
> My mistake - I gave you the wrong advice before. For MINSUPPLIES, I'm used
> to either a 1:1 UPS-to-server ratio, or 2:1 where the server can run with
> either power supply unpowered.
>
> I just tried
2019 Jun 09
2
How to shutdown macOS / mac OSX from Network UPS Tools client - NUT
On Sun, 9 Jun 2019, Joe Gervasio wrote:
> This question undermines my reading of the documentation. I had thought that
> these were separate things:
>
> SHUTDOWNCMD "/sbin/shutdown -u -h +1"
> NOTIFYCMD /opt/local/sbin/upssched
>
> I had assumed that the SHUTDOWNCMD would be used by the Nut client (upsmon) to
> shutdown the slave system, and that
2014 Jan 23
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 9:24 AM, Rafal Oleszek wrote:
> I tried all options:
> 1,2
> and in MINSUPPLIES: 1,2,3,4
> still didn't work.
My mistake - I gave you the wrong advice before. For MINSUPPLIES, I'm used to either a 1:1 UPS-to-server ratio, or 2:1 where the server can run with either power supply unpowered.
I just tried this in upsmon.conf:
MONITOR dummy1 1 monuser
2020 Aug 11
4
Synology NAS is shutting down Ubuntu servers after very brief power outage (fwd)
On Mon, 10 Aug 2020, Todd Benivegna wrote:
> synoups: https://hastebin.com/xexafofiha.bash
Wow! What a mess. It looks as if Synology wanted to write their own "NUT", but
decided it would be easier to put their ideas in a script when they saw they
could use upssched.conf to call it. NUT intends such a script for timer
management. Synology use it for general system management.
2017 Jan 11
3
NUT Client shuts down when performing runtime calibration on APC UPS
I've setup nas4free (latest version 11.0.0.4, which has NUT 2.7.4) in a VM and configured it via webinterface to my APC UPS and set "shutdown mode" to "UPS goes on battery" with a timer of 30s. Then I started runtime calibration on the UPS and after 30s nas4free has shut down! I think this is not the correct behavior, since the status was "OB CAL". The system
2017 Jun 29
2
Help with Elite 800VA usb UPS
On Jun 29, 2017, at 6:52 AM, Andrea de Lutti wrote:
>>> Anyway I still not receive any email on any test (power cord disconnected and/or reconnected for example)
>>
>> Oh, I misinterpreted "working script" as a script that was sending email, rather than work-in-progress. Does that same command work from the command line? Can you add something like "logger"