Displaying 20 results from an estimated 6000 matches similar to: "Server not shutting down before power loss"
2015 Dec 29
2
Server not shutting down before power loss
HI thanks for replying and helping.
I've now ran the UPS down a few times from full charge to test and I don't
think it's the batteries or a problem with the UPS itself. I can watch it
go from 100% right down to 1% over 20 minutes etc and then the power gets
so low that everything just powers off!
I think it's down to Nut not actually shutting down my server that is my
problem...
2015 Dec 29
0
Server not shutting down before power loss
> Hi I hope someone can please help.
>
> I have an Ubuntu Server running 14.04.3 LTS and using an APC ES550 UPS
> connected via USB.
>
> I've installed Nut and can see it does monitor the UPS correctly and give
> the correct stats with battery percentage etc.
>
> But on doing a "real" test and unplugging the UPS from the power supply,
> after watching
2023 Oct 28
1
My Back-UPS RS 1000 went haywire, any ideas?
Is the battery old? PbAc ones usually last for 2-3 years and then degrade.
Should be a field-replaceable part.
Some 20 years ago I had an APC BackUPS become a glorified power strip every
few years, so when the wall power disappeared - load went down immediately.
It was also beeping about battery replacement (but in the closet, was not
often noticed quickly). This is also a way for you to check if
2006 Nov 11
5
src/etc/rc.firewall simple ${fw_pass} tcp from any to any established
Hi security@ list,
In my self written, large ipfw rule set, I had something that passed
http to allow me to browse most but not all remote sites. For years
I assumed the few sites I had difficulty with were cases pppoed MTU
!= 1500, from not having installed tcpmssd on my 4.*-RELEASE, but
then running 6.1-RELEASE I realised that wasn't the problem.
http://www.web.de Still failed, &
2012 Dec 12
1
captive Portal Pfsense + FreeRadius + MySQL DBMS
Dear Friends Greetings,
i have a question for you, i am sure someone can help. The pfsense captive
portal is up and running. Time countdown vouchers are working without
issue, such as 30m, 45m, 1h & so on.
However, I'd like to set up a download quota of 200MB per voucher. but
then you need to login with a username and password, instead of vouchers.
but I haven't found a way to
2007 Jan 30
1
What about BIND 9.3.4 in FreeBSD in base system ?
http://www.isc.org/sw/bind/view/?release=9.3.4
SECURITY ADVISORIES
* CVE-2006-4095
CERT Vulnerability Note VU#915404
NISCC 172003
* CVE-2006-4096
CERT Vulnerability Note VU#697164
NISCC 172003
* CAN-2005-0034
NISCC-UNIRAS 20050125-00059
CERT Vulnerability Note VU#938617
[ODiP] == Dmitry Grigorovich
2013 Jul 03
2
UPS has no built-in monitor. [GishPuppy]
OS: Debian Wheezy
Nut: 2.6.4-2.3
Installation method: Synaptic
Device: CDP B-UPR505
Traces, debugs, etc.: Not available or irrelevant
Description:
Where I currently live (Honduras), buying a UPS with monitoring capability means spending at least twice as much as a "plain-Jane" model - usually even more than that. Thus, since I can't afford the ones with monitoring, all I have are
2018 Dec 03
2
MGE EllipseMAX 1500 shuts down after a few hours
I have taken out the batteries and measured them with a multimeter.
They put out 13V (they are rated 12V 9Ah).
Putting them back again and disconnecting the UPS from the mains it is
kept on, powering all the connected devices.
The shutdowns only occur when the UPS is being monitored. Are you sure
it's a battery problem? Do UPS perform further tests when they are
being polled for data?
2006 Sep 01
6
Slightly OT: Generators & UPS
Hi,
Can anyone shed some light on this:
My PC's are on a separate power circuit. Each PC has its own UPS.
I have an old Honda generator. When the power goes out, I fire up the
generator. However, the UPS's still run on battery. If I connect the
PC directly to the socket and bypass the UPS, the PC works.
I was told by a UPS supplier, that the power output from the
generator was
2007 Jun 06
2
security weakness
Hello Remko: sorry to bother you again,after e mailing freebsd-security@FreeBSD.org mailing list, got a reply by the list moderator rejecting my message,stating that there is no valid message from that address,sugesting yet another email address, it doubts the authenticity of your recomendation
Remko, you sugested I should look into securing my emailserver installation by preventing unauthorized
2009 Dec 07
1
Network admin
Does anyone need any remote administration (or local if you're in Portland,
OR)? I've been using freebsd on a daily basis for almost 2 years for
everything from a desktop system to running dns and apache. I'm also 2
semester's away from finishing my AAS in CIS: network admin, all A's. Oh,
did I mention I'll do it for free?
2013 Mar 07
1
unacceptable utility voltage rate of change
Hi,
One of my APC devices reports: "unacceptable utility voltage rate of change".
I believe it has something to do with input voltage fluctuating too fast maybe even beneath or over the input voltage thresholds.
Should I worry about this?
should I measure input voltage? (I suppose I'd need more than multimeter readings. Maybe an oscilloscope or a multimeter that can record
2020 Jan 24
2
System with MGE UPS shuts down too early
On January 24, 2020 6:13:31 PM GMT+02:00, "Georgi D. Sotirov" <gdsotirov at gmail.com> wrote:
>OK, my UPS turned out to be older that I thought. I apparently bought
>and installed it in September 2016 (not 2017 as I initially wrote).
>That
>makes for over 3 years of work, which is over the life expectancy of
>the
>batteries,
Good batteries can last 4-5 years.
2015 Feb 01
2
Start up script fails [/etc/killpower]
On 1/31/15, Charles Lepple <clepple at gmail.com> wrote:
> On Jan 31, 2015, at 3:09 PM, Melvin Call <melvincall979 at gmail.com> wrote:
>
>> One last question if you don't mind. I noticed the "default" POWERDOWNFLAG)
>> is
>> set to /etc/killpower, but I changed that to /tmp and modified my
>> umountroot
>> script to mount it read only
2020 Jan 11
4
System with MGE UPS shuts down too early
OK. I'll try it, but it really puzzles me how the battery could have
gone bad for just 15 months. The online power is pretty stable, so the
battery hasn't gone through many charge/discharge cycles...
Regards,
--
Georgi
On 11.1.2020 at 14:24, Manuel Wolfshant wrote:
>
> indicates that the UPS thought that battery was close to depleted and decided to shutdown. I suggest to fully
2015 Feb 01
0
Start up script fails [/etc/killpower]
On Feb 1, 2015, at 7:04 AM, Melvin Call <melvincall979 at gmail.com> wrote:
> Thank you Charles, for the assistance and the information. Everything is
> completely functional here now. Not sure if the APC BackUPS ES550 is on the
> list of compatible devices, but it works just fine with the usbhid-ups driver,
> and supports several basic commands.
You're welcome! We do have
2020 Oct 10
3
Multi UPS Monitoring
Hey all,
I've read through as many relevant mailing list posts and public blog posts
as I could, but I can't seem to find an answer to my issue.
I currently have 2x Tripp Lite SMART1500LCDXLs, and I am attempting to
monitor both of them with the same Raspberry Pi using NUT. The problem I
have is there doesn't seem to be any way in the nut.conf to
differentiate between the two UPS via
2013 Jul 03
0
UPS has no built-in monitor. [GishPuppy]
Hi, Reference:
lists.vn1 at gishpuppy.com wrote:
> OS: Debian Wheezy
> Nut: 2.6.4-2.3
> Installation method: Synaptic
> Device: CDP B-UPR505
> Traces, debugs, etc.: Not available or irrelevant
>
> Description:
>
> Where I currently live (Honduras), buying a UPS with monitoring capability means spending at least twice as much as a "plain-Jane" model - usually
2019 May 28
2
apc with rs232
On 5/28/19 3:39 PM, Julian H. Stacey wrote:
> grumpy at mailfence.com wrote:
>> a friend gave me an old apc smart-ups 1250
>> it has a rs232 interface but i have no pc with a rs232 port
>> i attempted to use a rs232 to usb adapter but the ups goes nuts
>> i connected the ups to batteries and verified it was working properly
>> when i plug the usb cable into the pc
2019 May 28
7
apc with rs232
a friend gave me an old apc smart-ups 1250
it has a rs232 interface but i have no pc with a rs232 port
i attempted to use a rs232 to usb adapter but the ups goes nuts
i connected the ups to batteries and verified it was working properly
when i plug the usb cable into the pc the ups shuts down
when i attempt to turn it on it beeps twice and shuts down
this all occurs before i start the nut software