similar to: nut UPS kill inverter: offdelay ignored

Displaying 20 results from an estimated 1100 matches similar to: "nut UPS kill inverter: offdelay ignored"

2014 Jul 26
4
Power race? with Eaton 5E and how to auto-mute beeper
I have a brand new Eaton 5E UPS purchased in Australia. Details: Eaton 5E Model: 5E650iUSB-AU Date: best I can find is the shipping date to supplier on box label - May 2014 OS: Ubuntu 14.04 Server edition Nut 2.7.1 Installed via apt-get install nut I have two problems I would like to fix. First the beeper is annoying and loud and I worry it will wake everyone up at night. I read that you can
2013 Mar 08
0
Windows: offdelay/ondelay
Are there plans to change the default offdelay/ondelay for the Windows versions of NUT since it can't be invoked at the end of shutdown? E.g. I have a Win2k3 server that takes just over 4min to shut down, so I set my offdelay to 600 (ondelay is +15 that) to be extra safe. Maybe a 2 min by default would be good? Most (all?) APC non-smart UPS's are hard-coded at an annoying 1min delay,
2018 Aug 22
0
APC Back-UPS CS 650 offdelay and startdelay
On Aug 21, 2018, at 1:37 PM, Karol Olszewski <karol.olszewski at ipflow.pl> wrote: > > I'm send debug file /lib/nut/usbhid-ups -a apc -DDD in attachement. > I tested two different ones APC BackUPS CS 650 and on both problem occurred. > I borrowed PowerWalker (driver blazer_usb), and all function + offdelay, > ondelay works perfectly. unfortunately, it looks like there
2018 Aug 26
0
APC Back-UPS CS 650 offdelay and startdelay
W dniu 24.08.2018 o 23:13, Karol Olszewski pisze: > Hi > I'm bit closer :) > Acctually change "UPS.Output.APCDelayBeforeReboot" to > >   { "shutdown.return", 0, 0, "UPS.Output.APCShutdownAfterDelay", NULL, > "90", HU_TYPE_CMD, NULL }, > > Now, UPS turn off load after 90 sec, but not power ON when power is back > Dear nut
2010 Nov 11
1
Setting offdelay and ondelay in Smart-UPS 1500 RM units
Hello there. Have been experimenting with an APC Smart-UPS 1500 RM and would like to share the results of my research. I hope this could be of help to people having this kind of units. I would also like to give something back to the NUT community. :) Here are the details of the unit in question (a 1500 VA rack mountable one): Model: Smart-UPS 1500 RM Firmware revision: 617.3.I USB firmware
2018 Aug 21
2
APC Back-UPS CS 650 offdelay and startdelay
Welcome, Acctualy, I'm try to poweroff my ESXi (6.7). Virtual machine with Ubuntu and redirected USB port with APC Back UPS CS 650, have nut-server and send info to ESXi. When battery is low, ESXi poweroff gracefully all VM and same ESX go down. This work fine and don't have any problem. But important to me, is set to more offdelay on UPS than the default 60 sec. (cut off power socket
2024 Mar 14
1
driver.parameter.offdelay vs ups.delay.shutdown / driver.parameter.ondelay vs ups.delay.start
Hi, My Cyber Power reports these two values. Each pair has the same value. Would they normally be the same thing? Thanks Alan
2024 Mar 16
0
driver.parameter.offdelay vs ups.delay.shutdown / driver.parameter.ondelay vs ups.delay.start
Thanks On Sat, 16 Mar 2024 at 18:57, Charles Lepple <clepple_at_gmail.com_chribonn at duck.com> wrote: > > On Mar 14, 2024, at 11:41?AM, Alan via Nut-upsuser <nut-upsuser at alioth-lists.debian.net> wrote: > > > Hi, > > > > My Cyber Power reports these two values. Each pair has the same value. > > > > Would they normally be the same thing? >
2018 Aug 22
2
APC Back-UPS CS 650 offdelay and startdelay
W dniu 22.08.2018 o 14:41, Charles Lepple pisze: > /lib/nut/usbhid-ups -a apc -DDD -k Please see attachement. -- Karol Olszewski ipflow.pl -------------- next part -------------- A non-text attachment was scrubbed... Name: APC_BackUPS_CS_650_fsd.log.gz Type: application/gzip Size: 5735 bytes Desc: not available URL:
2018 Aug 24
2
APC Back-UPS CS 650 offdelay and startdelay
W dniu 24.08.2018 o 13:10, Charles Lepple pisze: > Sorry, I didn't mean to imply that the master branch was necessarily going to be different, just wanted to make sure you had everything set up to recompile. The real test is to see if things change after commenting out that line (such as by changing it to start with "//"): > > // { "shutdown.return", 0, 0,
2018 Aug 23
0
APC Back-UPS CS 650 offdelay and startdelay
On Aug 22, 2018, at 1:20 PM, Karol Olszewski <karol.olszewski at ipflow.pl> wrote: > > W dniu 22.08.2018 o 14:41, Charles Lepple pisze: >> /lib/nut/usbhid-ups -a apc -DDD -k > Please see attachement. 1.872180 Report[buf]: (2 bytes) => 40 00 1.872196 Path: UPS.Output.APCDelayBeforeReboot, Type: Feature, ReportID: 0x40, Offset: 0, Size: 8, Value: 0 [...] 1.872439
2018 Aug 24
0
APC Back-UPS CS 650 offdelay and startdelay
On Aug 23, 2018, at 10:46 AM, Karol Olszewski <karol.olszewski at ipflow.pl> wrote: > > W dniu 23.08.2018 o 02:16, Charles Lepple pisze: >> >> For some reason, this is being hardcoded to 1: >> >> drivers/apc-hid.c- /* used by APC BackUPS CS */ >> drivers/apc-hid.c: { "shutdown.return", 0, 0, "UPS.Output.APCDelayBeforeReboot", NULL,
2018 Aug 23
2
APC Back-UPS CS 650 offdelay and startdelay
W dniu 23.08.2018 o 02:16, Charles Lepple pisze: > > For some reason, this is being hardcoded to 1: > > drivers/apc-hid.c- /* used by APC BackUPS CS */ > drivers/apc-hid.c: { "shutdown.return", 0, 0, "UPS.Output.APCDelayBeforeReboot", NULL, "1", HU_TYPE_CMD, NULL }, > > Can you rebuild the NUT drivers as described here?
2015 Jan 27
0
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
On Jan 22, 2015, at 9:53 AM, Sebastian Hosche <sebastian.hosche at web.de> wrote: > Hi Charles, > > Thanks so much for your quick and detailed reply! I've added my answers and details inline. Sorry this reply wasn't as quick. > On 22.1.2015 04:46, Charles Lepple wrote: >> On Jan 21, 2015, at 9:15 AM, Sebastian Hosche <sebastian.hosche at web.de> wrote:
2015 Jan 22
0
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
On Jan 21, 2015, at 9:15 AM, Sebastian Hosche <sebastian.hosche at web.de> wrote: > Hi there, > > I just purchased a CyberPower BR850ELCD and while setting NUT up with the install instructions from the homepage was pretty straightforward, and the UPS was detected by the usbhid-ups driver, I'm having problems getting the UPS to work properly. > > First issue: whatever I
2015 Jan 22
2
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
Hi Charles, Thanks so much for your quick and detailed reply! I've added my answers and details inline. On 22.1.2015 04:46, Charles Lepple wrote: > On Jan 21, 2015, at 9:15 AM, Sebastian Hosche <sebastian.hosche at web.de> > wrote: > >> First issue: whatever I set as the offdelay, seems to be ignored and >> the UPS just cuts the power about 2sec after receiving
2015 Jan 21
2
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
Hi there, I just purchased a CyberPower BR850ELCD and while setting NUT up with the install instructions from the homepage was pretty straightforward, and the UPS was detected by the usbhid-ups driver, I'm having problems getting the UPS to work properly. First issue: whatever I set as the offdelay, seems to be ignored and the UPS just cuts the power about 2sec after receiving the
2014 Aug 10
0
Power race? with Eaton 5E and how to auto-mute beeper
On Jul 26, 2014, at 9:58 AM, Leith Bade <leith at leithalweapon.geek.nz> wrote: > First the beeper is annoying and loud and I worry it will wake everyone up at night. I read that you can mute the beeper temporarily (and this works) but that most UPSs do not allow you to permanently turn it off (I tried using upsrw but it said beeper.status was read only). Can you send the variable list
2018 May 09
0
Tripp Lite SU5000RT3U
sorry, I thought I hit reply-all. CC'ing the list. On May 8, 2018, at 10:00 AM, Michael <fax12345 at gmail.com> wrote: > > Hi Charles, > > I'll gladly help where I can. I did reach out to their product support, and I did not have install the displaylink driver as that is for a totally different product, so ignore all that. > > The 208 V makes sense. The unit
2013 Dec 24
3
Delayed UPS start up after shutdown?
On 12/06/2013 10:57 PM, Kris Jordan wrote: > [...] > (*) Some UPS's do provide extra options to determine when they will > restore power to load. That would be a nice feature. Anyway, it is a strange thing that I can set the waiting time for power to be restored if main power comes back before offdelay has elapsed, but the UPS ignores this setting if main power comes back after