2015 Mar 19
0
Brand new EATON 3S700DIN (mfr.date 09/28/14) doesn't wait for LB flag
Sergey,
I?m no expert on this but I have been reading the driver code, trying to sort out bigger problems with the OpenUPS driver! I can make 2 observations that I can?t check out myself :
?beeper.disable? was previously ?beeper off? - and ?beeper.enable? was ?beeper.on?. Not sure if it?s worth trying the old versions?
If your UPS doesn?t wait for LB, could this be because there is another
2015 Jul 29
0
[Nut-upsuser] Brand new EATON 3S700DIN (mfr.date 09/28/14) doesn't wait for LB flag
Hi Philip,
I've updated NUT to 2.7.3 and finally found the root cause for the
unexpected shutdown:
It is recommended to increase pollinterval to 10 seconds in ups.conf for
usbhid-ups driver due to a known issue:
http://www.networkupstools.org/docs/man/usbhid-ups.html
Default DEADTIME=15 in upsmon.conf was triggering shutdown. Increasing the
value to 30 seconds resolved the issue.
Now when
2014 Jun 05
2
Question about voltage threshold setting in NUT
Hello Charles,
Thank you so much for your help. Just run upsc and it is possible that
input.transfer.low is the one because we used power regulator to bring down
the power around 84v and then the ups sent the power loss message to PC. Do
you think some others may take effect for the low voltage? Just have the
upsc result attached.
Then I retried input.transfer.low, default.input.transfer.low,
2014 Jun 05
0
Question about voltage threshold setting in NUT
Hey Charles,
Latest update. Looks like in ups.conf I setup default.input.transfer.low =
84. After I took that line out, restart upsdrvctl, upsmon, and upsd, the
command of
sudo upsrw -s input.transfer.low=70 -u * -p * ups
return OK. Still need to verify if it works by using voltage regulator and
will keep you updated.
Thank you for your help
Regards
Shen
On Thu, Jun 5, 2014 at 8:54 AM,
2013 Sep 10
1
[HCL] Eaton 5S1500LCD supported by usbhid-ups
Device Manufacturer: Eaton
Device Name: 5S1500LCD
----------------------------------------------------------
upsc output:
battery.charge: 100
battery.charge.low: 20
battery.runtime: 3515
battery.type: PbAc
device.mfr: EATON
device.model: Ellipse PRO 1500
device.serial: 0000000000
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
2013 Sep 10
1
[HCL] Eaton 5S1500LCD supported by usbhid-ups
Device Manufacturer: Eaton
Device Name: 5S1500LCD
----------------------------------------------------------
upsc output:
battery.charge: 100
battery.charge.low: 20
battery.runtime: 3515
battery.type: PbAc
device.mfr: EATON
device.model: Ellipse PRO 1500
device.serial: 0000000000
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
2017 Feb 20
2
[HCL] Powerware PW5125 with driver bcmxcp
This UPS is already listed in the compatibility list. But I wanted to
add the instant commands supported by upscmd:
============================
Instant commands supported on UPS [PW5125]:
beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
load.on - Turn on the load immediately
outlet.1.load.off - Turn off the load on
2014 Jul 26
4
Power race? with Eaton 5E and how to auto-mute beeper
I have a brand new Eaton 5E UPS purchased in Australia.
Details:
Eaton 5E
Model: 5E650iUSB-AU
Date: best I can find is the shipping date to supplier on box label - May
2014
OS:
Ubuntu 14.04 Server edition
Nut 2.7.1
Installed via apt-get install nut
I have two problems I would like to fix.
First the beeper is annoying and loud and I worry it will wake everyone up
at night. I read that you can
2023 Nov 22
1
APC Modbus support is finally here!
Jim Klimov via Nut-upsuser <nut-upsuser at alioth-lists.debian.net>
>
> Got an update for APC Modbus users: a new PR is waiting for real-life testing for settable variables and instant commands support.
>
> https://github.com/networkupstools/nut/pull/2184
>
> As before, a custom build of libmodbus may be needed for USB support (detailed in the earlier PR), but Serial and
2023 Nov 22
1
APC Modbus support is finally here!
Jim Klimov via Nut-upsuser <nut-upsuser at alioth-lists.debian.net>
>
> Got an update for APC Modbus users: a new PR is waiting for real-life testing for settable variables and instant commands support.
>
> https://github.com/networkupstools/nut/pull/2184
>
> As before, a custom build of libmodbus may be needed for USB support (detailed in the earlier PR), but Serial and
2023 Nov 27
1
APC Modbus support is finally here!
Jim Klimov <jimklimov+nut at gmail.com>
>
> I believe some fixes were applied to the branch since your report (most visibly, about battery time settings), are you in position to test how it behaves now? :)
Hi:
I got another ups for testing. so I test the new commit for both
APC SRT3000XL and SMT2200RM2U. the results below:
1. I get the new attribute "ups.test.result" for
2023 Nov 27
1
APC Modbus support is finally here!
Jim Klimov <jimklimov+nut at gmail.com>
>
> I believe some fixes were applied to the branch since your report (most visibly, about battery time settings), are you in position to test how it behaves now? :)
Hi:
I got another ups for testing. so I test the new commit for both
APC SRT3000XL and SMT2200RM2U. the results below:
1. I get the new attribute "ups.test.result" for
2008 Nov 04
1
Is SIPPEER curcalls working for you ?
Hi,
In this thread
http://lists.digium.com/pipermail/asterisk-users/2008-October/219592.html ,
I wondered whether SIPPEER curcalls was working.
I could test this anew today. Here are my findings :
Alice, Bob and Carol ar all using SIP Phones.
Whenever Alice is calling Bob,
- if Carol is calling Alice, SIPPEER(Alice:curcalls) equals 0
- if Carol is calling Bob, SIPPEER(Bob:curcalls) equals 1
2020 Sep 11
1
UPS recommendation for NUT and power-on-delay support
On Fri, Sep 11, 2020, at 4:05 PM, Bartosz wrote:
> Dear All,
>
> Could you please recommend me a UPS with 100% support of the ondelay parameter and NUT compatibility?
>
> 850 or 1000 VA
>
> I have the EATON 5E850iUSBDIN UPS and it does not support this parameter so I would like to buy another UPS that for sure will support it.
>
> Thank you,
> Bart
Can you tell
2023 Nov 22
1
APC Modbus support is finally here!
Great! Thanks for the info, and hope the driver author can address the nits
(forwarding now...)
Jim
On Wed, Nov 22, 2023, 15:05 d tbsky <tbskyd at gmail.com> wrote:
> Jim Klimov via Nut-upsuser <nut-upsuser at alioth-lists.debian.net>
> >
> > Got an update for APC Modbus users: a new PR is waiting for real-life
> testing for settable variables and instant commands
2023 Nov 22
1
APC Modbus support is finally here!
Great! Thanks for the info, and hope the driver author can address the nits
(forwarding now...)
Jim
On Wed, Nov 22, 2023, 15:05 d tbsky <tbskyd at gmail.com> wrote:
> Jim Klimov via Nut-upsuser <nut-upsuser at alioth-lists.debian.net>
> >
> > Got an update for APC Modbus users: a new PR is waiting for real-life
> testing for settable variables and instant commands
2014 Jun 05
0
Question about voltage threshold setting in NUT
On Jun 4, 2014, at 6:38 PM, Shen Chuan wrote:
> $ sudo upsrw -s battery.charge.low=70 -u * -p * ups
> OK
Not sure this does what you originally asked, though.
Does upsc show any settings related to sensitivity?
--
Charles Lepple
clepple at gmail
2010 Aug 20
2
APC Smart-UPS X 1500 Restart Issue.
APC Smart-UPS X 1500 Restart Issue.
Hi All,
I have installed nut-2.4.3. I have manually modified the files apc-hid.c
and udev-rules to support 5G APC UPS. I took sample code from the 2.5
development tree.
Shutdown process is working very well -- upsmon creates the file
/etc/killpower - shutdown script checks for the file and issues
/sbin/upsdrvctl shutdown - UPS cuts the power off. All
2010 Aug 20
2
APC Smart-UPS X 1500 Restart Issue.
APC Smart-UPS X 1500 Restart Issue.
Hi All,
I have installed nut-2.4.3. I have manually modified the files apc-hid.c
and udev-rules to support 5G APC UPS. I took sample code from the 2.5
development tree.
Shutdown process is working very well -- upsmon creates the file
/etc/killpower - shutdown script checks for the file and issues
/sbin/upsdrvctl shutdown - UPS cuts the power off. All
2023 Nov 24
1
APC Modbus support is finally here!
I believe some fixes were applied to the branch since your report (most
visibly, about battery time settings), are you in position to test how it
behaves now? :)
Thanks in advance,
Jim Klimov
On Wed, Nov 22, 2023 at 3:20?PM Jim Klimov <jimklimov+nut at gmail.com> wrote:
> Great! Thanks for the info, and hope the driver author can address the
> nits (forwarding now...)
>
> Jim