Displaying 20 results from an estimated 4000 matches similar to: "Question about voltage threshold setting in NUT"
2014 Jun 04
0
Question about voltage threshold setting in NUT
On Jun 3, 2014, at 5:16 PM, Shen Chuan wrote:
> We have an Eaton 3S 550 UPS using NUT tool to send power loss event. By default the power voltage threshold is set to 85 volts. If the voltage is less than 85 volts, it will trigger ONBATT event from NUT. Is there a way in NUT we can change the threshold from 85 volts to a lower voltage like 40 volts?
It might be possible with upsrw - try
2014 Jun 04
2
Question about voltage threshold setting in NUT
Hello Charles,
Thank you so much for your reply.
Yes. 40v was too low. In windows, those range started from 76v, 85v, and
96v. Just tried upsrw command to modify input.transfer.low and
input.transfer.boost.low. There were some error messages returned. Tried
another one battery.charge.low and it returns ok.
$ sudo upsrw -s input.transfer.low=70 -u * -p * ups
Unexpected response from upsd: ERR
2014 Jun 04
1
Question about voltage threshold setting in NUT
Hello,
We have an Eaton 3S 550 UPS using NUT tool to send power loss event. By
default the power voltage threshold is set to 85 volts. If the voltage is
less than 85 volts, it will trigger ONBATT event from NUT. Is there a way
in NUT we can change the threshold from 85 volts to a lower voltage like 40
volts?
We were trying to change ups.conf to modify the output of upsc ..., but
looks like it
2014 Jun 05
2
Question about voltage threshold setting in NUT
Hello Charles,
Thank you so much for your help. Just run upsc and it is possible that
input.transfer.low is the one because we used power regulator to bring down
the power around 84v and then the ups sent the power loss message to PC. Do
you think some others may take effect for the low voltage? Just have the
upsc result attached.
Then I retried input.transfer.low, default.input.transfer.low,
2014 Jun 05
0
Question about voltage threshold setting in NUT
Hey Charles,
Latest update. Looks like in ups.conf I setup default.input.transfer.low =
84. After I took that line out, restart upsdrvctl, upsmon, and upsd, the
command of
sudo upsrw -s input.transfer.low=70 -u * -p * ups
return OK. Still need to verify if it works by using voltage regulator and
will keep you updated.
Thank you for your help
Regards
Shen
On Thu, Jun 5, 2014 at 8:54 AM,
2014 Jun 05
0
Question about voltage threshold setting in NUT
On Jun 4, 2014, at 6:38 PM, Shen Chuan wrote:
> $ sudo upsrw -s battery.charge.low=70 -u * -p * ups
> OK
Not sure this does what you originally asked, though.
Does upsc show any settings related to sensitivity?
--
Charles Lepple
clepple at gmail
2014 Jun 05
2
Question about voltage threshold setting in NUT
Hey Charles,
Looks like after take out default.input.transfer.low, upsrw script *DOES*
work, the only thing for Eaton 3S 500 is that it is only accept certain
voltage values for input.transfer.low, 84v and 96v are two of them.
Otherwise the value never gets picked up.
Thank you for all your help
Shen
On Thu, Jun 5, 2014 at 12:07 PM, Shen Chuan <shen at minutekey.com> wrote:
> Hey
2014 Jun 06
2
Question about voltage threshold setting in NUT
On Jun 5, 2014, at 10:53 PM, Charles Lepple wrote:
> As you have seen, the "default.*" and "overwrite.*" names are not actual variables: they are configuration options to change what is returned from upsc. That is why you get VAR-NOT-SUPPORTED.
typo; should have been "override.*"
--
Charles Lepple
clepple at gmail
2014 Jun 06
0
Question about voltage threshold setting in NUT
Hello Charles,
Thank you for your reply.
For the discrete value thing, this morning I did try to run
sudo upsrw -s input.transfer.low=x -u * -p * ups
I changed "x" value from 60 to 96 then checked upsc result. All the script
return OK but only 84 and 96 got picked up and working.
Out model is Eaton 3S 500. And in windows it has a Eaton Personal Solution
Pac. In Battery transfer
2014 Jun 06
0
Question about voltage threshold setting in NUT
On Jun 5, 2014, at 4:22 PM, Shen Chuan wrote:
> Looks like after take out default.input.transfer.low, upsrw script DOES work, the only thing for Eaton 3S 500 is that it is only accept certain voltage values for input.transfer.low, 84v and 96v are two of them. Otherwise the value never gets picked up.
As you have seen, the "default.*" and "overwrite.*" names are not actual
2014 Jun 18
2
Question about recycle power of Tripp Lite UPS
Hello Charles,
Thank you for your comment. Just tried to use ups.delay.shutdown to
postpone the UPS shutdown. The thing is that if the PC shutdown first, then
the UPS, it wasn't able to send "shutdown.reboot" any more because
everything is power off after the UPS shuts down.
Also play on the watchdog for Tripp Lite. Looks like it has the command of
reset.watchdog but not
2014 Dec 01
0
Do I need to configure times and percents?
On Dec 1, 2014, at 4:11 AM, Victor Porton <porton at narod.ru> wrote:
> battery.voltage: 13.70
> battery.voltage.high: 13.00
> battery.voltage.low: 10.40
These are the voltage thresholds for the UPS, so theoretically the UPS will send the LB signal when the battery voltage goes lower than 10.40 Volts.
Also, if battery.charge works, you can use "ignorelb" if you want to
2017 May 14
2
[HCL] Cyber Power Systems CP1500AVRLCDa supported by usbhid-ups
[updated]
OpenBSD 6.1/amd64
NUT 2.7.4p0 (from OpenBSD package)
Results of upsc:
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 20
battery.mfr.date: CPS
battery.runtime: 2902
battery.runtime.low: 300
battery.type: PbAcid
battery.voltage: 26.9
battery.voltage.nominal: 24
device.mfr: CPS
device.model: CP1500AVRLCDa
device.serial: CTHGN200xxxx
device.type: ups
driver.name:
2014 Jun 17
3
Question about recycle power of Tripp Lite UPS
Hello,
We are trying to develop a mechanism to power cycle Tripp Lite UPS. When we
checked the upscmd, looks like the only command we can use is
shutdown.reboot(sudo upscmd -u user -p password ups shutdown.reboot).
Because the PC is connected to UPS directly and we would prefer shutdown PC
before power cycle the UPS. But if we run shutdown PC first it won't run
the power cycle the UPS script
2014 Jun 17
3
Question about recycle power of Tripp Lite UPS
Hello,
We are trying to develop a mechanism to power cycle Tripp Lite UPS. When we
checked the upscmd, looks like the only command we can use is
shutdown.reboot(sudo upscmd -u user -p password ups shutdown.reboot).
Because the PC is connected to UPS directly and we would prefer shutdown PC
before power cycle the UPS. But if we run shutdown PC first it won't run
the power cycle the UPS script
2017 May 22
3
[HCL] Cyber Power Systems CP1500AVRLCDa supported by usbhid-ups
On 5/21/2017 10:39 AM, Charles Lepple wrote:
> Mike,
>
> Thanks for the info. I have enough to add an entry to the DDL, but I have a few more questions inline.
>
> On May 14, 2017, at 1:21 PM, Mike wrote:
>>
>> [updated]
>>
>> OpenBSD 6.1/amd64
>> NUT 2.7.4p0 (from OpenBSD package)
>>
>>
>> Results of upsc:
>>
>>
2014 Dec 01
2
Do I need to configure times and percents?
01.12.2014, 06:18, "Charles Lepple" <clepple at gmail.com>:
> On Nov 29, 2014, at 7:32 AM, Victor Porton <porton at narod.ru> wrote:
>> ?On Debian Linux jessie:
>>
>> ?After buying an UPS and installation of nut-server and nut-client at my PC and configuring the ports and the protocol, do I need to adjust time and/or percentage parameters, to be sure my
2014 Jun 11
1
Setting the transfer threshold voltage on a TrippLite OMNI900LCD
At the company I work for, we are using many TrippLite OMNI900LCD UPSs and
are having difficulty setting the lower transfer threshold voltage. On our
other model, the Eaton MGE-3S550, this can be set using upsrw to set the
input.transfer.lowsetting, but on the Omni900, this option is not
available. In our testing, it defaults to ~95v but we want to set it to 84v.
More info:
- OS = OpenSuse 13.1
-
2014 Jun 18
0
Question about recycle power of Tripp Lite UPS
[moving this to nut-upsuser, since other users of Tripp Lite equipment may have specific experience with this.]
On Jun 17, 2014, at 7:51 PM, Shen Chuan <shen at minutekey.com> wrote:
> We are trying to develop a mechanism to power cycle Tripp Lite UPS. When we checked the upscmd, looks like the only command we can use is shutdown.reboot(sudo upscmd -u user -p password ups
2007 Sep 04
1
Tripplite Smart 2200 and Battery Voltage
For my Smart 2200, a charged battery string is anywhere between 25.6 and
26.8 volts. I'm seeing nut report 13.0 volts, which seems suspicious. Even
if the UPS were reporting half of the actual battery voltage to keep
protocol compatibility with models having a 12V battery system, the value
of exactly 13.0 seems unlikely.
According to the page at