similar to: false alerts/shutdown

Displaying 20 results from an estimated 7000 matches similar to: "false alerts/shutdown"

2006 Dec 27
3
Help with nut 2.0.4, MGE Ellipse 1000 and FreeBSD
Hello. So as my english is not so good, i'll try to write my story in bash commands :o) miwa@zork3$ uname -mrs FreeBSD 5.5-STABLE i386 miwa@zork3$ su root@zork3# cd /usr/ports/sysutils/nat root@zork3# make && make install root@zork3# cd ../nut-usb root@zork3# make && make install root@zork3# cd /usr/local/etc/nut root@zork3# cat ups.conf user=root [MGE-Ellipse]
2017 Apr 07
2
[Eaton 5S 1500] overvoltage shut down?
>> last night we had what looked like a power spike and 3 machines plugged >> into 2 Eaton UPS went down instantly. I heard the click the UPS makes when >> it shuts the load on the ports and then shuts itself down (ie same thing if >> I simulate with upsmon -fsd). The machines instantly came back, there was no >> actual downtime, and the machine next to them which is
2007 Oct 24
4
MGE Ellipse 800 shutdown problems - using upsmon NOTIFYCMD
upsmon.conf using NOTIFCMD and NOTIFYFLG is working well, it is calling my script "notify" on requested events (ONBATTERY,LOWBATTERY and ONLINE). Command #upsmon -c fsd -u monmaster myups at localhost gracefully shutdown my box and after several seconds switch off the ups's load. Two problems: - notify script is called and executed as user "nut" (as it used to be
2007 Jan 09
1
Differences between newhidups (MGE tables) in 2.0.4 and svn trunk
I was looking at how other drivers deal with outlet collections, and I noticed some differences between newhidups in 2.0.4 (from Debian's 2.0.4-2.3) and the SVN trunk (rev 723) on an Evolution. Full diff is below, but here are the highlights: * MGE HID 0.9 vs 1.0 * outlet.#.switch seems to have moved to the commands outlet.#.load.{on,off} Then I found this in the ChangeLog: * fix
2013 Dec 24
0
Delayed UPS start up after shutdown?
Angel Tsankov wrote, On 12/24/2013 1:22 AM: > On 12/06/2013 10:57 PM, Kris Jordan wrote: > > [...] >> (*) Some UPS's do provide extra options to determine when they will >> restore power to load. > > That would be a nice feature. > > Anyway, it is a strange thing that I can set the waiting time for > power to be restored if main power comes back before
2007 Feb 01
2
NUT-2.0.3 - problems on setting values
Hello, we have a MGE Pulsar Evolution 800 connected to a Fedora Core5 Server using a serial cable. Installed and configured properly are RPM versions of nut-2.0.3-0.1.fc5 nut-client-2.0.3-0.1.fc5 nut-cgi-2.0.3-0.1.fc5 which all work (mostly) fine. The server is connected to outlet.0 and properly shuts down when it's loosing power after around 20 minutes. It also boots up whenever the ups
2014 Jun 05
2
Question about voltage threshold setting in NUT
Hello Charles, Thank you so much for your help. Just run upsc and it is possible that input.transfer.low is the one because we used power regulator to bring down the power around 84v and then the ups sent the power loss message to PC. Do you think some others may take effect for the low voltage? Just have the upsc result attached. Then I retried input.transfer.low, default.input.transfer.low,
2006 Jun 09
1
MGE ellipse 1200 config and documentation
Hi, I have recently purchased MGE ellipse 1200 UPS for my home system. Obviously, the choice of this particular brand was mainly dictated by MGE's long-standing support for Linux and NUT project. The fact that the box was clearly the prettiest looking one on the block did help also ;-). I have had NUT tools installed and configured in no time, as I did it numerous times before -- kudos
2006 May 16
2
MGE Pulsar Extreme communication problems
Hi, I am trying to talk to an MGE Pulsar Extreme UPS over RS232 with the mge-shut driver but I'm having some problems. It appears to init OK but I can't, say, turn the outlets off, eg.. harrow:~>upsc mge@localhost battery.charge: 78 battery.charge.low: 20 battery.runtime: 05760 driver.name: mge-shut driver.parameter.port: /dev/cuad1 driver.version: 2.0.3 driver.version.internal: 0.65
2006 Jun 27
3
Setting MGE powershare attributes
Hi! We have two MGE Evolution 1100 here, and I want to make use of the powershare outlets to force a particular boot sequence on the machines powered by them. However I'm not sure how to set those variables upon NUT starting, without having to change the init scripts to call "upsrw". Is there some place where I can set them, where they can be read automatically on startup? One of
2013 Dec 24
3
Delayed UPS start up after shutdown?
On 12/06/2013 10:57 PM, Kris Jordan wrote: > [...] > (*) Some UPS's do provide extra options to determine when they will > restore power to load. That would be a nice feature. Anyway, it is a strange thing that I can set the waiting time for power to be restored if main power comes back before offdelay has elapsed, but the UPS ignores this setting if main power comes back after
2005 Aug 19
1
MGE Ellipse 800 USBS doesn't shutdown under FreeBSD
Hi all, First of all thanks for the great work on nut ! (despite it's not fully functional yet overhere). Everything seemed to go fine until the final test : shutdown the UPS ! The system is running FreeBSD 5.3, the UPS is MGE Ellipse 800 USBS both linked with the MGE serial cable. The system is a remote server, only running some file services and large disks. The porting,
2006 May 12
1
Various NUT issues/questions
Hi, FINALLY got my UPS working, YEA!!!! But now it brings up even more issues.. (BOOO!!) 1) I'm thinking this is a UPS issue, but when I pull the plug on my UPS, it goes from 100 to 30 in just a short amount of time (Minutes). This causes the machine to shut down. But once it gets to 0, its beeped its little heart out for a few more HOURS providing power to the non-system items perfectly.
2008 Jan 07
1
Working platform with FreeBSD + USB + MGE Ellipse (usbhid-ups)
Hi, I've have had some difficulties to run NUT on freebsd, but I finally managed to have something that work reliably enough. For those who may be interested, here is what I did. Os: FreeBSD 6.2-RELEASE-p7, nut: 2.2.0, libusb: 0.1.12 First, I had to patch libusb with the changes submitted by Nevil Thatcher in the nutups forum in may 2006. Without this change, nothing works.
2014 Jun 05
0
Question about voltage threshold setting in NUT
Hey Charles, Latest update. Looks like in ups.conf I setup default.input.transfer.low = 84. After I took that line out, restart upsdrvctl, upsmon, and upsd, the command of sudo upsrw -s input.transfer.low=70 -u * -p * ups return OK. Still need to verify if it works by using voltage regulator and will keep you updated. Thank you for your help Regards Shen On Thu, Jun 5, 2014 at 8:54 AM,
2009 Oct 10
3
MGE NMC and NutShutdownModule (and other stuff)
Hi all, some time ago I bought at discount price a NMC for managing a few computers using the programmable outlets features available on my MGE Evolution, unuseful otherwise (ATM). However, expecially for my server machine, I don't like very much the NSM client provided by MGE/Eaton and I'd rather use only NUT from my distribution. So, looking at the netxml-ups driver, I started adding
2006 Jul 13
2
MGE Pulsar Extreme - restart problem
Hello, looking for replacements for some older Powerware equipment I found the MGE Pulsar Extreme 1000C and I'm currently testing one with nut-2.0.3 on a self-brewn i386-linux. Upto now everything seems to work fine - except I can't get the power outlets switching on again after mains returns. As this works with Personal Solution-Pac 2 on W2k I thought that there might be a way to
2017 Mar 23
5
Fatal EEPROM fault!
Hello, Sorry if any of this is obvious - I'm new to NUT. NUT via upsc is displaying (edited for length): device.model: Eaton 5P 2200 device.type: ups driver.name: usbhid-ups ups.alarm: Fatal EEPROM fault! ups.status: ALARM OL CHRG ups.test.interval: 604800 ups.test.result: Done and passed driver.version: 2.7.2 driver.version.data: MGE HID 1.33 driver.version.internal: 0.38 Is this possibly
2013 Sep 19
0
UPS compatibility list
Luke-Jr wrote, On 9/18/2013 1:02 PM: > I wanted to suggest some rating for functionality. I got the UPS available > that seemed to have the best possible rating from NUT's list (Eaton Powerware > UPS 1500), and found out it doesn't support telling me battery level or > runtime! :/ I'm avoiding Eaton/Powerware because the lack of usbhid support, the bcmxcp driver
2008 Oct 04
3
Joining forces with the Network UPS Tools
Hi Powermen ;-) I recently came across the Powerman project (http://sourceforge.net/projects/powerman/), pointed by Tony Merenda, from Opengear (thanks Tony). Congrats for your work in this area! I've thought a bit about Powerman and NUT since then... NUT currently supports hosts of UPSs and few PDUs (RPCs), and provides tons of features: http://test.networkupstools.org