Setting offdelay and ondelay in Smart-UPS 1500 RM units
Hello there. Have been experimenting with an APC Smart-UPS 1500 RM and would like to share the results of my research. I hope this could be of help to people having this kind of units. I would also like to give something back to the NUT community. :) Here are the details of the unit in question (a 1500 VA rack mountable one): Model: Smart-UPS 1500 RM Firmware revision: 617.3.I USB firmware
2013 Dec 06
0
Delayed UPS start up after shutdown?
Angel Tsankov wrote, On 12/6/2013 12:31 PM: > Hello, Ren?. > >> You can change the parameter >> ups.delay.start into your UPS to set the "Interval to wait before >> (re)starting the load (seconds)" >> >> use upsset to change the value. > > So far, the ups.delay.start parameter in my MGE Protection Center 675 > has always been equal to the
2024 Mar 16
0
driver.parameter.offdelay vs ups.delay.shutdown / driver.parameter.ondelay vs ups.delay.start
Thanks On Sat, 16 Mar 2024 at 18:57, Charles Lepple <clepple_at_gmail.com_chribonn at duck.com> wrote: > > On Mar 14, 2024, at 11:41?AM, Alan via Nut-upsuser <nut-upsuser at alioth-lists.debian.net> wrote: > > > Hi, > > > > My Cyber Power reports these two values. Each pair has the same value. > > > > Would they normally be the same thing? >
2015 Jun 30
1
nut UPS kill inverter: offdelay ignored
Dear All, I am running Slackware64-14.1(Linux marto 3.10.17 #1 SMP Fri Feb 14 16:39:21 CST 2014 x86_64 Intel(R) Pentium(R) CPU G3250 @ 3.20GHz GenuineIntel GNU/Linux) with kernel 3.10.17 and nut package nut-2.6.5-x86_64-1_SBo, buit from source using the build script http://slackbuilds.org/repository/14.1/system/nut/ In the README.Slackware it is suggested that the commands for killing the
2018 Aug 21
2
APC Back-UPS CS 650 offdelay and startdelay
Welcome, Acctualy, I'm try to poweroff my ESXi (6.7). Virtual machine with Ubuntu and redirected USB port with APC Back UPS CS 650, have nut-server and send info to ESXi. When battery is low, ESXi poweroff gracefully all VM and same ESX go down. This work fine and don't have any problem. But important to me, is set to more offdelay on UPS than the default 60 sec. (cut off power socket
2018 Feb 02
0
Default value for ondelay
On Fri, 2 Feb 2018, nut.user.u830 at neverbox.com wrote: > I have an older box set up this way for continuous integration, and it needs to see more than a few seconds of power loss for the "always turn > on" BIOS setting to work. I forget how many different intervals I tried, but 30 seconds of off time is reliable for that particular box. > > Thanks. This
2019 Apr 05
3
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
Hi, I have the Eaton 5E850iUSBDIN UPS connected via USB to a Raspberry Pi 3B+. It seems that everything but the ondelay parameter works so far. when I test the setup with this command: upsmon -c fsd The NUT server makes the NUT clients shut down properly and the Raspberry Pi running the NUT server shuts down correctly too. The problem is that after UPS shuts down, it immediatelly brings the
2013 Dec 24
0
Delayed UPS start up after shutdown?
Angel Tsankov wrote, On 12/24/2013 1:22 AM: > On 12/06/2013 10:57 PM, Kris Jordan wrote: > > [...] >> (*) Some UPS's do provide extra options to determine when they will >> restore power to load. > > That would be a nice feature. > > Anyway, it is a strange thing that I can set the waiting time for > power to be restored if main power comes back before
2024 Mar 14
1
driver.parameter.offdelay vs ups.delay.shutdown / driver.parameter.ondelay vs ups.delay.start
Hi, My Cyber Power reports these two values. Each pair has the same value. Would they normally be the same thing? Thanks Alan
2018 Aug 22
0
APC Back-UPS CS 650 offdelay and startdelay
On Aug 21, 2018, at 1:37 PM, Karol Olszewski <karol.olszewski at ipflow.pl> wrote: > > I'm send debug file /lib/nut/usbhid-ups -a apc -DDD in attachement. > I tested two different ones APC BackUPS CS 650 and on both problem occurred. > I borrowed PowerWalker (driver blazer_usb), and all function + offdelay, > ondelay works perfectly. unfortunately, it looks like there
2018 Aug 26
0
APC Back-UPS CS 650 offdelay and startdelay
W dniu 24.08.2018 o 23:13, Karol Olszewski pisze: > Hi > I'm bit closer :) > Acctually change "UPS.Output.APCDelayBeforeReboot" to > >   { "shutdown.return", 0, 0, "UPS.Output.APCShutdownAfterDelay", NULL, > "90", HU_TYPE_CMD, NULL }, > > Now, UPS turn off load after 90 sec, but not power ON when power is back > Dear nut
2013 Dec 24
3
Delayed UPS start up after shutdown?
On 12/06/2013 10:57 PM, Kris Jordan wrote: > [...] > (*) Some UPS's do provide extra options to determine when they will > restore power to load. That would be a nice feature. Anyway, it is a strange thing that I can set the waiting time for power to be restored if main power comes back before offdelay has elapsed, but the UPS ignores this setting if main power comes back after
2015 Jan 22
0
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
On Jan 21, 2015, at 9:15 AM, Sebastian Hosche <sebastian.hosche at web.de> wrote: > Hi there, > > I just purchased a CyberPower BR850ELCD and while setting NUT up with the install instructions from the homepage was pretty straightforward, and the UPS was detected by the usbhid-ups driver, I'm having problems getting the UPS to work properly. > > First issue: whatever I
2013 Dec 06
2
Delayed UPS start up after shutdown?
Hello, Ren?. > You can change the parameter > ups.delay.start into your UPS to set the "Interval to wait before > (re)starting the load (seconds)" > > use upsset to change the value. So far, the ups.delay.start parameter in my MGE Protection Center 675 has always been equal to the driver.parameter.ondelay parameter (which equals the ondelay argument in ups.conf).
2018 Aug 23
2
APC Back-UPS CS 650 offdelay and startdelay
W dniu 23.08.2018 o 02:16, Charles Lepple pisze: > > For some reason, this is being hardcoded to 1: > > drivers/apc-hid.c- /* used by APC BackUPS CS */ > drivers/apc-hid.c: { "shutdown.return", 0, 0, "UPS.Output.APCDelayBeforeReboot", NULL, "1", HU_TYPE_CMD, NULL }, > > Can you rebuild the NUT drivers as described here?
2015 Jan 22
2
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
Hi Charles, Thanks so much for your quick and detailed reply! I've added my answers and details inline. On 22.1.2015 04:46, Charles Lepple wrote: > On Jan 21, 2015, at 9:15 AM, Sebastian Hosche <sebastian.hosche at web.de> > wrote: > >> First issue: whatever I set as the offdelay, seems to be ignored and >> the UPS just cuts the power about 2sec after receiving
2018 Mar 02
1
Work around for power recycling after shutdown.return - TSSHARA UPS - nutdrv_qx driver - megatec protocol
2018-02-28 21:11 GMT+01:00 Jairo Rotava <jairo.rotava at gmail.com>: > Hello, > > I think that on this file nutdrv_qx_megatec.c the definition for > shutdown.stayoff may be wrong. In the file the definition is "S%sR0000\r"m > while on the megatec protocol description ( > http://networkupstools.org/protocols/megatec.html) the command is just > "S%s\r".
2005 Dec 19
1
MGE Pulsar ES 8+
Hi! I have a MGE Pulsar ES 8+ UPS. Here is the response of some commands: - Si --> 3000 44 0 - Si 1 --> Pulsar ES8+ 0 - Ai --> 5 0 It's not recognized very well by the current (from CVS) mge-utalk driver: [root@srv01 ~]# /home/rog/src/nut/drivers/mge-utalk -i 20 -DDD -u root /dev/ttyS0 Network UPS Tools - MGE UPS SYSTEMS/U-Talk driver 0.86 (2.1.0) debug level is '3'
2015 Jan 21
2
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
Hi there, I just purchased a CyberPower BR850ELCD and while setting NUT up with the install instructions from the homepage was pretty straightforward, and the UPS was detected by the usbhid-ups driver, I'm having problems getting the UPS to work properly. First issue: whatever I set as the offdelay, seems to be ignored and the UPS just cuts the power about 2sec after receiving the
2018 Oct 04
0
after power outage and proper shutdown, UPS turns on before power returns
On Oct 3, 2018, at 8:13 PM, Gabriel <jarod125 at gmail.com> wrote: > > On Tue, Oct 2, 2018 at 3:59 PM Charles Lepple <clepple at gmail.com> wrote: >> >> On Sep 27, 2018, at 6:59 PM, Gabriel <jarod125 at gmail.com> wrote: >>> >>> Hi, >>> >>> I'm struggling with a peculiar issue with my UPS. After a power >>>