similar to: no serial number for Tripp-Lite SMART3000RM2U?

Displaying 20 results from an estimated 4000 matches similar to: "no serial number for Tripp-Lite SMART3000RM2U?"

2014 May 16
2
Tripp Lite SMART3000RM2U (protocol 3003) running time and charge?
Hello, I own an older Tripp Lite SMART3000RM2U (protocol 3003). It does not work with usbhid-ups but it mostly works with the tripplite_usb driver (nut 2.7.1, the latest in the Gentoo tree), in the sense that the status (on line, on battery, etc.) is detected correctly, the machine is shut down on critical battery, and I can even get some information from the UPS. This is how it all looks:
2007 Jun 29
1
SMART3000RM2U problems with nut 2.0.5
Has anyone gotten this model of tripp-lite to work? sudo /usr/local/bin/upsdrvctl -DDDDD -u root start Network UPS Tools - UPS driver controller 2.0.5 Starting UPS: tripplite exec: /usr/local/bin/tripplite_usb -a tripplite Network UPS Tools - Tripp Lite OMNIVS and SMARTPRO driver 0.7 (2.0.5) Warning: This is an experimental driver. Some features may not function correctly. Detected a UPS: TRIPP
2012 May 09
3
SMART3000RM2U?
Can anyone point me to information for getting the Tripplite SMART3000RM2U to work with NUT? Our newer Tripplite units seem to work with the usbhid-ups driver, but these older ones seem to need something different. So far I have had little success getting tripplite_usb to work. [root at banyan ~]# tripplite_usb -a tripplite Network UPS Tools - Tripp Lite OMNIVS / SMARTPRO driver 0.20 (2.6.1)
2014 May 16
0
Tripp Lite SMART3000RM2U (protocol 3003) running time and charge?
On May 15, 2014, at 9:39 PM, Stefan Bruda wrote: > What bugs be though is that I cannot seem to be able to read the > remaining run time on battery. The battery charge is also widely > inaccurate (it drops to zero really fast and stays there). I read > somewhere that the usb.debug numbers may hold the key to this (at > least to the running time that is), but I don't know what
2014 Jun 03
0
Tripp Lite SMART3000RM2U (protocol 3003) running time and charge?
On Jun 2, 2014, at 10:25 PM, Stefan Bruda wrote: > Hello, > > At 15:42 -0400 on 2014-6-1 Charles Lepple wrote: >> >> On May 24, 2014, at 5:49 PM, Stefan Bruda wrote: >> >>>> Don't worry about the battery physical properties for now - the >>>> problem there is that we don't have enough information from the UPS >>>> to do a
2014 Jun 01
0
Tripp Lite SMART3000RM2U (protocol 3003) running time and charge?
On May 24, 2014, at 5:49 PM, Stefan Bruda wrote: >> Don't worry about the battery physical properties for now - the >> problem there is that we don't have enough information from the UPS >> to do a proper calculation. With the V_interval[] settings, you can >> tweak the new state-of-charge calculation to match what you see via >> upsc when the battery is
2014 May 20
0
Tripp Lite SMART3000RM2U (protocol 3003) running time and charge?
On May 19, 2014, at 7:12 PM, Stefan Bruda wrote: > Hello, > > First of all thank you so much for the information. No problem, glad it is useful. > [...] > Therefore as far as my UPS is concerned s_value[5] is wildly > incorrect. So it turns out that the RM15002U also does not report anything useful for s_value[5]:
2014 May 22
2
Tripp Lite SMART3000RM2U (protocol 3003) running time and charge?
Hello, At 22:19 -0400 on 2014-5-19 Charles Lepple wrote: > > On May 19, 2014, at 7:12 PM, Stefan Bruda wrote: > > > Therefore as far as my UPS is concerned s_value[5] is wildly > > incorrect. > > So it turns out that the RM15002U also does not report anything useful for s_value[5]: > >
2014 Jun 03
2
Tripp Lite SMART3000RM2U (protocol 3003) running time and charge?
Hello, At 15:42 -0400 on 2014-6-1 Charles Lepple wrote: > > On May 24, 2014, at 5:49 PM, Stefan Bruda wrote: > > >> Don't worry about the battery physical properties for now - the > >> problem there is that we don't have enough information from the UPS > >> to do a proper calculation. With the V_interval[] settings, you can > >> tweak
2014 May 19
2
Tripp Lite SMART3000RM2U (protocol 3003) running time and charge?
Hello, First of all thank you so much for the information. At 22:43 -0400 on 2014-5-15 Charles Lepple wrote: > > On May 15, 2014, at 9:39 PM, Stefan Bruda wrote: > > > What bugs be though is that I cannot seem to be able to read the > > remaining run time on battery. The battery charge is also widely > > inaccurate (it drops to zero really fast and stays
2014 May 23
0
Tripp Lite SMART3000RM2U (protocol 3003) running time and charge?
On May 22, 2014, at 10:03 AM, Stefan Bruda wrote: >> >> Does battery_voltage_nominal get set correctly? Theoretically, it >> should be 48, since the 2nd and 3rd digits of ups.debug.V are 08, >> and that gets multiplied by 6. > > Yes, as it appear as 48V in the output of upsc. Good. > >> Might be useful to have an intermediate value that doesn't scale
2006 Jun 27
1
Tripp Lite OMNIVS1500XL Unknown protocol
Good afternoon, I'm trying without much success to monitor a Tripp Lite OMNIVS1500XL using NUT. I checked the compatibility list and saw that this UPS is supported by tripplite_usb. The system is running Debian Stable, but I've downloaded NUT 2.0.3 and compiled from source since the packaged 2.0.1 doesn't include tripplite_usb. I compiled --with-user=nut. My first attempt at
2014 May 24
3
Tripp Lite SMART3000RM2U (protocol 3003) running time and charge?
Hello, At 09:24 -0400 on 2014-5-23 Charles Lepple wrote: > > See attached. Still doesn't have the writable V_interval values, > but I probably won't have time to test that until later. Thank you for the patch. > Don't worry about the battery physical properties for now - the > problem there is that we don't have enough information from the UPS > to do a
2006 Oct 13
2
Tripp-Lite OmniVS1500XL
All, I recently purchased a Tripp-Lite OmniVS1500XL and am running NUT on a Centos-based system. Based on the compatibility list I specified the tripplite_usb driver. When I query the unit I get: [root@chryxus ~]# upsc UPS@localhost battery.voltage.nominal: 24 driver.name: tripplite_usb driver.version: 2.0.3-pre2 driver.version.internal: 0.6 input.voltage.nominal: 120
2006 Feb 08
3
Tripp Lite is up to no good
Well, I have good news and bad news. I have a Tripp Lite SmartPro UPS attached to a Linux server running Ubuntu 5.10, and I'm running the just-released nut 2.0.3. I had error -71 from the UPS, which Charles Lepple correctly called out as a likely cable problem (thank you, Charles.) The cable provided with the UPS by Tripp Lite was just plain bad. Not too long, mind you- defective. I
2006 Sep 18
3
tripp lite SMART2200RMXL2U -- empty ups.status
Hello. I'm new to nut and don't know if I've missed something in setting it up or if my ups isn't quite supported. I'm using these: - svn version of nut (downloaded on 9/13/06) - a tripp lite SMART2200RMXL2U - debian sarge with 2.6.8 kernel - the tripplite_usb driver (newhidups says my ups is not supported) I figured out how to get the device perms correct.
2012 Dec 07
2
Tripp Lite SMART1000RM2U
Hi, I recently purchased a Tripp Lite SMART1000RM2U UPS (http://www.tripplite.com/en/products/model.cfm?txtSeriesID=744&txtModelID=2657) and tried to configure the NUT with tripplite_usb driver and encounter the following problems: 1. battery.charge doesn't report correct charge level when the UPS is On Batter. It just reports 0. Even though it will report 100 when on line power. 2. I
2007 May 11
1
Tripp Lite SMART2200RMXL2U and Fedora Core 6 (NUT 2.0.3)?
Hi, I'm running Fedora Core 6 and need to monitor a Tripp Lite SMART2200RMXL2U. I've loaded the nut-2.0.3-2.1 RPM. The UPS is connected via the provided USB cable, and that much appears to work: # dmesg | grep -i tripp hiddev96: USB HID v1.10 Device [Tripp Lite TRIPP LITE SMART2200RMXL2U ] on usb-0000:00:1f.4-2 # lspci | grep -i usb 00:1f.4 USB Controller: Intel Corporation 82801BA/BAM
2006 Jan 13
1
help with TRIPP LITE SMART550USB
Hi I have a Tripp lite smartusb550 using fedora 3 (2.6.12-1.1381_FC3smp). Managed to establish communication with the ups using the tripplite_usb driver but get the following errors Any help to make it work will be appreciated cheers Julio -----------------------------------------------------------------------------------------------------------------------------------------------------
2014 Jun 26
1
The dreaded Tripp Lite SMART500RT1U and NUT
<nut-upsuser at lists.alioth.debian.org> I am doing my best to avoid have to spend $280 for a network monitoring card to put into a $190 UPS just to have some good remote monitoring capabilities. Rather, I would like to monitor my many 1U Tripp Lite's on my network using a Raspberry Pi running Raspian and using NUT. However, I cannot seem to get it working. And I while the hardware